Further information for Dold 0067701 MH9353.11 AC0,5-5A UH=AC230V current transducer
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
1 C/O contact
Width
45 mm
Type
MH 9353
Operate delay
Variant
Auxiliary voltage
AC 230 V
Contact equipping
1 changeover contact
Measuring range
AC 0,5 - 5 A
Terminal type
screw terminal fixed
The current transducer MH9353.11 from Dold is a combined device consisting of a measuring relay and a transducer, used for monitoring the current consumption of electrical consumers in enclosure applications. The device operates on the idle current principle, where the output relay drops out as soon as the set threshold value is exceeded. It features a galvanically isolated analog output as well as a relay output with a changeover contact. The auxiliary voltage is AC 230 V, and the terminal type is a fixed screw terminal. The width is 45 mm, enabling compact mounting in standard enclosures.
Applications
The MH9353.11 is designed for continuous monitoring of electrical consumers in the range of AC 0.5 to 5 A. It is typically used in industrial plants, machine controls, or energy distribution systems to detect overloads or power failures early. The galvanic isolation of the analog output enables safe and interference-free signal transmission to higher-level control or monitoring systems. The integrated LED indicator displays the status of the auxiliary voltage and the relay switching position, enabling quick diagnosis during operation.
Functions and Equipment in Detail
The device offers an adjustable threshold value in the range of 0.5 to 5 A, which can be set continuously using a rotary switch. The hysteresis is fixed and is less than 5 % of the set value, ensuring stable switching behavior. The response time is under 350 ms, allowing the device to react quickly to changes in current consumption. The LED indicator shows rapid flashing in case of overload in the current range, providing a visual warning. The measurement accuracy is ±2 % of the nominal measurement value, which is sufficient for industrial applications.
Technology Explained Simply
The current transducer operates with a measurement range of AC 0.5 to 5 A and is designed for a nominal frequency of 50/60 Hz. The frequency range extends from 45 to 400 Hz, covering a wide range of application scenarios. The overload capacity is continuously 16 A and up to 25 A for short durations (under 10 seconds). The analog output is galvanically isolated and offers selectable signals of 0…20 mA and 0…10 V or 4…20 mA and 2…10 V, with selection achieved by bridging terminal X1 with G. Galvanic isolation is tested at AC 3750 V between auxiliary, measurement, and output circuits, ensuring high safety.
Compatibility and Accessories
The device is specified according to IEC/EN 60255-1 and designed for continuous operation. It is intended for use in enclosures and requires no additional mounting accessories. Optional plug-in terminal blocks are available, enabling quick device replacement. The terminal type is standard fixed screw terminal, although spring-cage terminals are also available as an alternative. Power supply is via AC 230 V, with permissible voltage fluctuations between 0.8 and 1.1 times the nominal voltage.
Mounting and Installation
Mounting is performed in an enclosure with a width of 45 mm. The connection terminals are designed for fixed screw terminals, and wiring must follow the manufacturer’s connection diagrams. For currents exceeding the maximum continuous input value, an external current transformer must be connected in series. The operating temperature range is from -20 °C to +60 °C, with storage temperature up to +70 °C. The operating altitude is limited to a maximum of 2000 m above sea level.
Advantages in Operation
The MH9353.11 combines the functions of a measuring relay and a transducer in a single device, reducing wiring and simplifying installation. The simple adjustment of the threshold value via a rotary switch allows application-specific customization. The galvanic isolation of the analog output ensures safe signal transmission, and the LED indicator provides quick visual control of the operating status. The mechanical life is 30 million switching operations, while the electrical life at 3 A and AC 230 V is 200,000 switching operations, ensuring high reliability in industrial use. Short-circuit resistance is defined with a maximum fuse rating of 4 A gG/gL according to IEC/EN 60947-5-1.