Technical data
1- / 2-channel2
ApprovalsUL
Cat. / PL acc. to EN ISO 13849-14/e
ConnectionFront side cage clamp terminals
Output contacts max.3 NO contacts
SIL CL acc. to IEC/EN 620613
SIL acc. to IEC/EN 620613
Thermal current Ith max.8 A
Width17,5 mm
TypeUF 6925
Cross fault detectionYes
Suited as safety gate monitorYes
Variant
Contact equipping2 NO contacts, 1 NC contact
Nominal voltageDC 8 - 36 V
Approvals and MarkingsUL-listed C/US, TÜV
VariantSwitching capacity standard. Start-Mode adjustable. Cross fault detection adjustable
The emergency stop module UF6925.22/61 DC8-36V from Dold is a safety-oriented switching component designed for use in industrial systems, particularly in conjunction with emergency stop pushbuttons and safety doors. It enables the safe enabling and interruption of a safety circuit and is designed for applications where the safety of personnel and machinery is paramount. The device features a 2-channel architecture and is designed for operating voltages in the range of DC 8 to 36 V. The width is 17.5 mm, making it suitable for use in compact enclosures.

Applications
This module is intended for safety-critical applications, particularly in industrial automation, where it is used as part of a safety concept. It can be used in systems complying with EN 61511 as well as in combustion systems according to EN 50156-1. The approval as a safety door monitor allows its use in systems where opening a safety door must trigger the shutdown of machines or drives. Integration into safety circuits is achieved via forced-guided output contacts, ensuring secure signal transmission.

Functions and Equipment in Detail
The module features contact configuration with 2 NO contacts and 1 NC contact, where up to 3 NO contacts can be used as output contacts. The connection technology uses front-mounted spring-cage terminals, enabling quick and secure installation. The operating mode can be set via switch (S2) between manual and automatic single-function mode. Additionally, short-circuit detection in the control circuit can be enabled via another switch (S1) to detect wiring faults such as short circuits. The operating status is indicated by LED indicators for channel 1, channel 2, and power supply.

Technology Explained Simply
The safety function of the module is based on a 2-channel design with forced-guided contacts, ensuring secure signal transmission. Short-circuit detection identifies faults in the control circuit caused by accidental connections between wires. The start function can be activated manually (e.g., via an emergency stop pushbutton) or automatically (e.g., after voltage restoration), depending on requirements. The maximum thermal current rating is 8 A, allowing use in systems with corresponding loads. The operating voltage range of DC 8 to 36 V makes the module flexible for use in various industrial environments.

Compatibility and Accessories
The module is designed for use with emergency stop pushbuttons and safety doors. It is suitable for systems complying with EN 61511 and EN 50156-1, with specific configurations varying according to application scenarios. The approvals UL-listed C/US and TÜV, along with compliance with standards EN ISO 13849-1 (PL e, Category 4) and IEC/EN 62061 (SIL 3), ensure suitability for safety-critical applications. Integration into existing safety architectures is achieved via the designated connection terminals and defined interfaces.

Mounting and Installation
Mounting is performed in standard control panels or enclosures. The front-mounted spring-cage terminals allow for quick and secure wiring connections. The width of 17.5 mm requires minimal space, enabling integration into compact control systems. The terminal assignment is detailed in the datasheet, with clear definitions for contact assignments (NO, NC) and control circuits. Installation must follow the manufacturer’s technical instructions to fully ensure safety functions.

Advantages in Operation
The module offers high safety integrity through approval up to PL e / Category 4 and SIL 3, making it suitable for demanding applications. The narrow width and front-mounted connection technology simplify installation and maintenance. Adjustable functions such as start mode and short-circuit detection allow flexible adaptation to different requirements. The LED indicators provide a quick overview of the operating status, supporting fault diagnosis. Use in safety door applications and combustion systems demonstrates the module’s versatility across various industrial sectors.