Dold 0067529, EAN: 4030641675295

Dold 0067529 UG9461PM DC24V 8AI/2AO analog input/output module

Dold 0067529 UG9461PM DC24V 8AI/2AO analog input/output module

Lieske Part No. 1000967
Mfg Part No 0067529
EAN-Code 4030641675295
Manufacturer Dold
Here only 495,98 EUR
590,22 EUR incl. VAT

Further information for Dold 0067529 UG9461PM DC24V 8AI/2AO analog input/output module

Technical data
Bus interfaceModbus RTU
Enclosure designSwitch cabinet
Number of inputs/outputs2 analogue outputs, 8 analogue inputs
Width22,5 mm
TypeUG 9461
Variant
Auxiliary voltageDC 24 V
Terminal typeplug in mixed terminals
Variant2 analog outputs 0 - 10 V. 2 analog inputs 0 - 10 V or 0 - 20 mA. 2 thermocouple inputs Typ K. 4 thermistor inputs Pt1000
The Dold UG9461PM DC24V 8AI/2AO is a universal input/output module for industrial applications, designed for use in enclosures. It is used for capturing and transmitting analog measurement values, particularly temperatures, and enables communication via a Modbus RTU interface. The device is designed for use in automation and control systems, where it serves as an interface between sensors and higher-level controllers.

Applications
This module is suitable for use in industrial environments where temperature measurement using Type K thermocouples and Pt1000 thermistors is required. It can also be used for capturing voltage and current signals in the range of 0–10 V and 0–20 mA respectively. Application areas include, for example, process monitoring in manufacturing, building automation, or monitoring of machines and plants, where continuous measurement values must be captured and transmitted via Modbus to a control system.

Functions and Equipment in Detail
The module features a total of 8 analog inputs and 2 analog outputs. The inputs are partially configurable: two inputs can be set to 0–10 V or 0–20 mA, two inputs are designated for Type K thermocouples, and four inputs are designed for Pt1000 thermistors. The analog outputs provide a voltage signal in the range of 0–10 V. Configuration of the inputs is done via three rotary switches, which set the Modbus address and baud rate. Device functions are indicated by 13 LEDs, including a green LED for supply voltage, a red LED for faults, and yellow LEDs for bus status as well as individual inputs and outputs.

Technology Explained Simply
The auxiliary voltage is DC 24 V, with the voltage range allowed to be between 0.8 and 1.1 times the nominal voltage. The nominal power consumption is 2 W. Temperature measurements from Type K thermocouples are captured in the range of -180 °C to +1350 °C, with an internal resolution of 24 bits. For Pt1000 thermistors, a measurement range of -50 °C to +200 °C is specified, also with 24-bit resolution. The analog inputs for voltage and current have a resolution of 10 bits. Accuracy at 25 °C is ±0.5 °C for temperature sensors. The update time for temperature sensors is 650 ms, while analog inputs for voltage and current have an update time of 4 ms. Input resistances are ≥1 MΩ for temperature sensors, ≥100 kΩ for voltage inputs, and 500 Ω for current inputs. The measurement principles are integrating, ensuring high stability of the measured values.

Compatibility and Accessories
The module is designed for communication via Modbus RTU according to specification V1.1b3. The Modbus address and baud rate can be set via rotary switches, with baud rates ranging from 1200 to 115200 bit/s available. Response time depends on the baud rate and is up to 50 ms at 1200 bit/s. Communication takes place via Modbus signals A and B, which can be passed through via TWIN terminal blocks to forward auxiliary voltage and the bus to subsequent modules. The terminal blocks are plug-in and mixed-type, enabling flexible and quick installation.

Mounting and Installation
The module has a width of 22.5 mm and is designed for installation in enclosures. Installation is done via plug-in terminals, which allow for easy wiring. Terminal designations are clearly defined: A1 and A2 for auxiliary voltage, A and B for the Modbus bus, IN0 and IN1 for configurable analog inputs, +TC0/-TC0 and +TC1/-TC1 for thermocouples, +R0/-R0 to +R3/-R3 for thermistors, and OUT0 and OUT1 for analog outputs. Device settings are adjusted via rotary switches, which are directly accessible on the device.

Advantages in Operation
The module features a compact design and easy commissioning. The status indicators via 13 LEDs enable quick fault diagnosis. The TWIN terminal blocks simplify wiring in longer bus topologies. The configurable inputs and support for Modbus RTU make the module flexible for use in various automation systems. Measurement accuracy and value stability due to integrating measurement principles ensure reliable data transmission. Compliance with the standard IEC/EN 61131-2 ensures standardized integration into industrial control systems.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0