Dold 0067527, EAN: 4030641675271

Dold 0067527 UG5124.82PS trip circuit monitor DC20-60V

Dold 0067527 UG5124.82PS trip circuit monitor DC20-60V

Lieske Part No. 1000791
Mfg Part No 0067527
EAN-Code 4030641675271
Manufacturer Dold
Here only 330,88 EUR
393,75 EUR incl. VAT

Further information for Dold 0067527 UG5124.82PS trip circuit monitor DC20-60V

Technical data
Enclosure designSwitch cabinet
Output contacts2 C/O contacts
Width22,5 mm
TypeUG 5124
Variant
Auxiliary voltageDC 20 - 265 V
Contact equipping2 changeover contacts
Measuring current5 mA
Measuring voltageDC 20 - 60 V
The UG 5124 trip circuit monitor from Dold is an electronic monitoring device for control and trip circuits in electrical installations. It is used for continuous monitoring of power circuit breakers, disconnectors, and signal circuits to detect faults such as interruption of the trip coil, wire breaks, increased contact resistance, welded control contacts, or missing auxiliary voltage. The device operates on the principle of rest current and uses a constant current source that injects a measurement current of 5 mA into the circuit to be monitored. Galvanic isolation between the measurement circuit and the evaluation unit allows the use of different voltage sources. The width is 22.5 mm, enabling compact installation in enclosures.

Applications

The UG 5124 is specifically designed for monitoring trip circuits in industrial and stationary electrical installations. It is used to ensure the reliability of power circuit breakers and other switching devices. Continuous monitoring helps detect potential failures early, before they lead to system failure. Applications include power supply systems, industrial controls, switchgear, and safety circuits.

Functions and Equipment in Detail

The device features two changeover contacts as output contacts, which can be used for signaling states and controlling other components. The pickup delay is adjustable from 0 to 9 seconds in 1-second steps, and the drop-out delay is adjustable from 0 to 4 seconds in 1-second steps. These settings prevent false fault signals during brief actuation of the power switch. The repeatability of the time delays is ±2 % of the set value.

Technology Explained Simply

The trip circuit monitor operates with a measurement current of 5 mA, which flows through the contacts to be monitored. If this current cannot flow due to a fault, the relay activates. The constant current source ensures that power consumption in the measurement circuit remains independent of voltage, limiting power loss. Galvanic isolation between the measurement circuit and the evaluation unit allows the use of different voltage sources. Indication is provided by three LEDs: a green LED indicates the presence of auxiliary voltage, a yellow LED indicates a fault-free state (steady) or blinks during the drop-out delay, and a red LED indicates a fault (steady) or blinks during the pickup delay.

Compatibility and Accessories

The device is designed for an auxiliary voltage range of DC 20 to 265 V. The measurement voltage range is DC 20 to 60 V. The minimum voltage UAmin is DC 20 V. The output contacts are rated for a thermal current load of up to 4 A per contact. Switching capacity is AC 15: 3 A / AC 230 V for make contacts and 1 A / AC 230 V for break contacts, and DC 13: 1 A / DC 24 V. The electrical life is 1.5 × 10⁵ switching operations at 1 A and AC 230 V. The device is manufactured in accordance with IEC/EN 60255-1.

Mounting and Installation

The trip circuit monitor is mounted in enclosures. The width of 22.5 mm allows for compact placement. Connections are made via plug-in, coded terminal blocks, enabling quick replacement of the device. Terminal designations are: A1+ and A2 for auxiliary voltage, M1+ and M2 for the measurement circuit, and contacts 15, 16, 18 for relay 1 and 25, 26, 28 for relay 2. Adjustment of time delays is done via rotary switches on the front panel.

Operational Advantages

The UG 5124 offers a wide auxiliary voltage range of DC 20 to 265 V, allowing adaptation to various installation conditions. Galvanic isolation and the constant current source ensure reliable and energy-efficient monitoring. Separate settings for pickup and drop-out delays increase flexibility and prevent false alarms. The clear LED indication simplifies fault diagnosis. The plug-in, coded terminal blocks allow quick replacement without tools, speeding up maintenance and repair. The device is designed for use in industrial environments and complies with IEC/EN 60255-1 standards.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1000791