| Technical data |
| Bus interface | Modbus RTU |
| Enclosure design | Switch cabinet |
| Number of inputs/outputs | 4 relay outputs, 8 digital inputs |
| Width | 22,5 mm |
| Type | UG 9460 |
| Variant |
| Auxiliary voltage | DC 24 V |
| Contact equipping | 4 NO contacts |
| Terminal type | plug in mixed terminals |
| Variant | 8 digital inputs. 4 relay outputs |
The UG 9460 input / output module from Dold is a digital I/O module for use in enclosures, communicating with higher-level controls via a Modbus RTU interface. It features 8 digital inputs for DC 24 V and 4 relay outputs, with three of the outputs having a rated continuous current of 8 A and one of 16 A. The auxiliary voltage is DC 24 V, and the module is designed for continuous operation. The width of 22.5 mm allows for compact mounting in standard switchboards.
Applications
This module is suitable for capturing status information in industrial plants, for example from end switches, pushbuttons, or sensors. The digital inputs can receive signals from the plant and forward them via Modbus to a higher-level control system. The relay outputs are used to control actuators such as contactors, valves, or other electrical loads. The Modbus RTU interface enables easy integration into existing automation and measurement systems.
Functions and equipment in detail
The 8 digital inputs are designed for a voltage range of DC 10 to 30 V and comply with the IEC/EN 61131-2 standard. The outputs consist of 4 normally open contacts, with an electrical life of 1.5 x 10⁵ switching operations at AC 230 V and 5 A. The mechanical life exceeds 10⁸ switching operations. The outputs can be individually switched on and off via Modbus. Status indication is provided by 15 LEDs: a green LED indicates operational status, a red LED flashes in case of errors (e.g. Modbus communication error), and yellow LEDs indicate the status of inputs and outputs. Error code 9 indicates a Modbus communication error.
Technology explained simply
The module operates with an auxiliary voltage of DC 24 V, supplied via terminals A1 (+) and A2 (0 V). Modbus communication takes place via signal terminals A and B. The baud rate and Modbus address can be set using three rotary switches on the device. The TWIN connection terminals allow the auxiliary voltage and bus signal to be passed through, simplifying installation in existing switchgear. The plug-in mixed terminals provide a secure and quick connection.
Compatibility and accessories
The module is designed for use in enclosures and can be mounted in standard switchboards. The Modbus RTU interface is widely used and enables communication with a wide range of control and visualization systems. Compliance with the IEC/EN 61131-2 standard ensures a standardized interface for automation technology.
Mounting and installation
Mounting is done in an enclosure, with the width of 22.5 mm allowing for compact placement. The plug-in terminals simplify wiring. The Modbus address and baud rate are set using the rotary switches on the device. The TWIN terminals support passing through auxiliary voltage and bus, simplifying installation in existing plants.
Advantages in operation
The module is characterized by its compact design and easy commissioning. The clear status indication via 15 LEDs enables quick fault diagnosis. The Modbus RTU interface ensures reliable communication with higher-level controls. The plug-in terminals and TWIN connection terminals reduce installation time and increase flexibility during installation. The operating temperature range is between -20 °C and +50 °C, and the storage temperature range is between -40 °C and +70 °C. The relative humidity is up to 93 % at 40 °C, and the operating altitude is limited to below 2000 m. The EMC characteristics include electrostatic discharge of 8 kV (air discharge) and high-frequency radiation up to 2.5 GHz at 3 V/m, ensuring high immunity to interference. The rated impulse voltage is 6 kV between output contact and logic, and 4 kV between outputs, according to IEC 60664-1.