Further information for Dold 0067521 UG9410PM 3AC200-480V 5A 0-10S motor starter Modbus RTU
Technical data
1- / 3-phase
3
Auxiliary voltage
DC 24 V
Bus interface
Modbus RTU
Load current up to
5 A
Load voltage up to
3AC 200 - 480 V
Width
22,5 mm
Type
UG 9410
Temperature monitoring
Variant
Nominal current
5 A
Nominal voltage
3AC 200 - 480 V
Ramp time
0 - 10 s
Terminal type
plug in mixed terminals
The intelligent motor starter UG 9410 from Dold is a compact device for controlling and protecting 3-phase asynchronous motors. It enables soft start, soft stop, reversing, and motor protection, and is designed for rated voltages of 3AC 200 to 480 V and a rated current of 5 A. The width is 22.5 mm, enabling space-saving installation in enclosures. The device features a Modbus RTU interface, allowing parameterization and monitoring via an automation system. The control voltage is DC 24 V, and the load voltage can reach up to 3AC 200–480 V. The ramp time for start and stop is adjustable between 0 and 10 seconds.
Applications
The UG 9410 is designed for industrial applications, particularly in drives for door and gate controls, bridge drives, lifting mechanisms, conveyor systems, and positioning drives in process engineering. It is suitable for 3-phase motors with a power rating of 0.18 kW to 2.2 kW at 400 V. The soft start and soft stop functions reduce mechanical stress and extend the service life of drive components. Reversing is achieved via relays, which are switched without current to ensure high service life.
Functions and Equipment in Detail
The device offers up to seven functions in one module: forward rotation, reverse rotation, soft start, soft stop, motor protection, phase sequence monitoring, and phase failure monitoring. Communication monitoring ensures the reliability of control. Temperature monitoring is performed via a thermal model that measures current in one phase and calculates motor temperature. In case of overheating, the motor is switched off. Additionally, an external thermal switch can be used. Status indication is provided by five LEDs, displaying operating status, faults, and direction of rotation.
Technology Explained Simply
Soft start is implemented using thyristors, which phase-control two motor phases, allowing current and torque to rise gradually. This prevents jerking during start-up. Soft stop works similarly, with current and torque decreasing continuously. Ramp time and start voltage are adjustable via Modbus. The relay switching for reversing is done without current, increasing relay service life. Galvanic isolation between control and main circuits enhances safety. The voltage rating of the semiconductors is up to 1500 V, ensuring high operational safety.
Compatibility and Accessories
The device complies with IEC/EN 60947-4-2 standards. The Modbus RTU interface enables integration into existing automation systems. The TWIN connection terminal allows passing through of control voltage and bus, simplifying installation. Plug-in mixed terminals enable flexible and quick wiring. Modbus address and baud rate settings are adjusted via three rotary switches.
Mounting and Installation
The motor starter is mounted in standard control panels with a 35 mm mounting profile. The width of 22.5 mm allows for compact placement. The connection terminals are plug-in, ensuring quick and secure wiring. Control voltage (DC 24 V) and bus line are connected via the TWIN connection terminal. Main lines (L1, L2, L3) and motor connections (T1, T2, T3) are connected to the respective terminals. Parameterization is done via Modbus, allowing settings such as ramp time, start voltage, and baud rate to be configured.
Operational Advantages
The UG 9410 offers high device availability through semiconductor temperature monitoring, overload protection, and high voltage rating. Current-free relay switching extends service life. Simple commissioning and user-friendly operation via Modbus parameterization reduce installation time. The integrated motor protection function with thermal model protects the motor from overload. Phase sequence and phase failure monitoring increase operational safety. The width of 22.5 mm reduces space requirements by up to 80% compared to conventional solutions. Galvanic isolation between control and main circuits enhances operational safety.