Technical data
Enclosure designFront panel mounting
Width96 mm
TypeEH 5861
Variant
VariantFor LK 5896
The display instrument EH5861/005 from Dold is a specific accessory for the insulation monitor LK 5896 and serves for the external display of the current insulation resistance of a network against earth. It is directly connected to the analog output of the LK 5896 and displays the resistance value in kΩ. The device is designed for front panel mounting and has a width of 96 mm, making it suitable for standard control panels with a 96 mm module width. The dimensions are 96 mm (width) × 96 mm (height) × 52 mm (depth), allowing it to be integrated into standard enclosures.

Applications

The display instrument is primarily intended for the visual monitoring of insulation resistances in ungrounded AC, DC, and AC/DC networks. It is used particularly in installations where continuous and visible display of the insulation status is required, such as in photovoltaic systems, including those with thin-film technology, UPS systems, networks with frequency converters, battery networks, or in hybrid and battery-powered vehicles. The display enables quick fault localization and supports the preventive fire and system protection function of the LK 5896.

Functions and Equipment in Detail

The device displays the current insulation resistance in kΩ, with the display provided via an LED strip. This LED strip enables a user-friendly, visual representation of the current resistance value. The display is directly connected to the analog output of the LK 5896, which provides the insulation resistance value as a voltage or current signal (0...10 V / 0...20 mA or 2...10 V / 4...20 mA). The display instrument is therefore not an independent measuring device, but complements the function of the LK 5896 by providing a visible representation of the measured value.

Technology Explained Simply

The display instrument uses the analog output signals from the LK 5896, which are proportional to the measured insulation resistance. The signal type (voltage or current) can be set via the terminals XA/GA on the LK 5896. The EH5861/005 converts this signal into a visual display, with the LED strip showing the resistance value in kΩ. The display operates continuously as long as the LK 5896 is active and the analog outputs are enabled. The function is independent of the operating mode of the LK 5896; display is also possible with a de-energized network, provided the LK 5896 is supplied with auxiliary voltage.

Compatibility and Accessories

The display instrument EH5861/005 is designed exclusively for use with the insulation monitor LK 5896. It is not suitable for other devices or systems. The connection is made via the analog output of the LK 5896, with the signal type (voltage or current) being set on the LK 5896. There are no additional accessories specifically intended for the display instrument. Integration is direct into the existing LK 5896 installation.

Mounting and Installation

The device is designed for front panel mounting and is installed in a control panel with a module width of 96 mm. Mounting is done by securing it to the front plate of the control panel, with the electrical connection made via the network cable to the analog output of the LK 5896. No additional mounting aids or tools are required, as the connection terminals are standardized. Installation follows the guidelines for the LK 5896, with the signal type on the LK 5896 being set according to the requirements of the EH5861/005.

Advantages in Operation

The visual display of the insulation resistance allows for quick and immediate assessment of the insulation condition. This supports maintenance and fault diagnosis, especially in complex installations such as photovoltaic systems or hybrid vehicles. The display is independent of the operating mode of the LK 5896 and can also function with a de-energized network, provided auxiliary voltage is available. Integration into existing systems is simple, as no additional pre-stage devices or adapters are required. The LED strip provides a clear, easy-to-read representation of the resistance value, which is also visible from a distance.

Standards and Regulations

The display instrument is not an independent measuring device, but complements the function of the LK 5896, which is designed according to IEC/EN 61557-8 for insulation monitoring. The display therefore occurs indirectly via the analog signals from the LK 5896, which are captured according to this standard. The display itself is not subject to specific standards, as it merely visually represents the signals from the LK 5896.

Use in Specific Installations

In photovoltaic systems, especially those with thin-film technology, displaying the insulation resistance is important to respond early to insulation faults. In hybrid and battery-powered vehicles, the display enables quick fault localization, even when the inverter is switched off, since the LK 5896 can monitor even with a de-energized network. In UPS systems or networks with frequency converters, the visual display supports continuous monitoring and maintenance.