Further information for Dold 0066996 RL9854.11/61 AC45-135V 4-20% 0-30S voltage relay
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
AC 300 V
Output contacts
1 C/O contact
Width
35 mm
Type
RL 9854
Operate delay
Variant
Contact equipping
1 changeover contact
Hysteresis
4 - 20 %
Operating voltage
AC 45 - 135 V
Switching delay
0 - 30 s
Approvals and Markings
UL-listed C/US
Variant
De-Energized on trip
The voltage relay RL9854.11/61 from Dold is a device for monitoring single-phase AC networks with an operating voltage range of AC 45 to 135 V. It is used for detecting overvoltage, undervoltage, and voltage range exceedances in networks with 50/60 Hz. The device operates on the stand-by current principle, in which the output relay is energized in the normal state and de-energizes in the event of a fault. The functions can be easily selected via a function selector switch, without requiring complex menu structures.
Applications
This relay is suitable for monitoring AC networks in industrial and technical installations. It can be used, for example, for early detection of impending failures to avoid costly damage. The application also includes switching to a safety power supply after detection of a fault condition. The devices are designed for use in installation distributors and comply with the standard IEC/EN 60255-1.
Functions and equipment in detail
The device features an adjustable switching voltage, an adjustable hysteresis range of 4 to 20 % for re-energizing in the normal state, and an adjustable switching delay of 0 to 30 seconds. The hysteresis ensures that the relay does not switch uncontrollably due to minor fluctuations in the voltage range. Voltage range monitoring allows setting a range U ± ρU in percent, where the alarm is triggered as soon as the voltage leaves this range. The drop-out hysteresis is half the set ρU value.
Technology explained simply
The operating voltage of the relay is in the range of AC 45 to 135 V, with a nominal voltage of up to AC 300 V. The frequency range coverage extends from 45 to 65 Hz. The device consumes approximately 7 VA during operation. The output contacts consist of a changeover contact (1 C/O contact) with an AgNi contact material. The switching voltage is AC 250 V. Indication is provided via LEDs: a green LED ON" lights up when operating voltage is present, a red LED ">U" indicates overvoltage, and a red LED "<U indicates undervoltage. When the set voltage is exceeded, the corresponding LED blinks; after the switching delay has elapsed, it lights continuously and the output relay de-energizes. When the voltage returns to the desired range, the LED turns off immediately and the relay re-energizes.
Compatibility and accessories
The relay is designed for use in single-phase AC networks. It is equipped with a function selector switch that allows selection between overvoltage, undervoltage, and voltage range monitoring. The devices are designed for installation in installation distributors with a mounting width of 35 mm. The certifications include UL-listed C/US.
Mounting and installation
The device is mounted in installation distributors. The connection terminals are provided for phase voltage (L), neutral conductor (N), and changeover contacts (11, 12, 14). Mounting is done without additional auxiliary voltage, which reduces installation effort. Settings are adjusted via rotary controls for switching voltage, hysteresis, and switching delay.
Advantages in operation
The simple adjustment and clear indication of fault conditions enable quick fault detection. Preventive maintenance is supported by early detection of voltage anomalies, increasing the operational safety and availability of the system. High repeatability and a wide measurement voltage range ensure reliable results. The device is suitable for use in industrial environments where stable and continuous power supply is required.