Further information for Dold 0066988 residual current monitor type B 0-10s
Technical data
Adjustable measuring ranges
0,01 - 3 A
Approvals
UL
Classification
Type B (AC, DC even and pulsating)
Enclosure design
Distribution board
Type of voltage
AC, DC
Width
52,5 mm
Type
RN 5883
Broken conductor detection
Clear key
Operate delay
Relay contact / output
Test key
Variant
Auxiliary voltage
AC/DC 24 - 80 V
Contact equipping
1 changeover contact for prewarning, 1 changeover contact for alarm
Measuring range
10 - 3000 mA
Time delay
0 - 10 s
Approvals and Markings
UL-listed C/US, CCC
Variant
For current transformer ND5015/024, ND5015/035. Without analogue output
The Dold differential current monitor RN5883.12/61 is an all-current-sensitive monitoring switch for earthed networks, used for early detection of insulation faults. The device operates according to the Type B principle and detects differential currents with both AC and DC components. Measurement is performed via an external current transformer, with the RN5883.12/61 variant specifically designed for the current transformers ND5015/024 and ND5015/035. The auxiliary voltage is AC/DC 24 to 80 V, and the device is designed for use in installation distributors. It has a width of 52.5 mm and is suitable for use in industrial plants where continuous monitoring of insulation quality is required.
Applications
The differential current monitor RN5883 is used in earthed AC/DC networks to detect insulation faults early, before failure or damage occurs. It is particularly suitable for installations requiring high availability, such as in manufacturing, energy supply, or medical facilities. Since the device does not automatically switch off but only indicates, it enables targeted maintenance without shutting down the entire system. The application is in combination with an external current transformer, which detects the differential current and transmits it to the device.
Functions and Equipment in Detail
The device features two relay outputs: one changeover contact for pre-alarm and one changeover contact for alarm. Both are latching, so the state is retained even after a power failure. The LED display indicates operational readiness, pre-alarm, and alarm. An LED bar graph shows the current differential current, providing the user with a visual overview of the current insulation quality. The measurement ranges are adjustable and range from 10 mA to 3000 mA (0.01 to 3 A). The time delay is also adjustable and can be set between 0 and 10 seconds to avoid false triggering. A test button allows checking the function, and a reset button clears the alarm and pre-alarm indication.
Technology Explained Simply
The differential current monitor RN5883 operates on the principle of differential current measurement, detecting the difference between incoming and outgoing current. In case of an insulation fault, part of the current flows through the insulation to ground, which is detected as differential current. The device is all-current-sensitive, meaning it detects both AC and DC components, including pulsating DC voltage. The wire break detection ensures that a broken measurement circuit is recognized to avoid false alarms. The response delay prevents short-term triggering caused by transient disturbances. The transparent cover protects the adjustment controls from unintended changes.
Compatibility and Accessories
The RN5883.12/61 is specifically designed for the current transformers ND5015/024 and ND5015/035. These transformers are required to detect the differential current and transmit it to the device. The variant without analog output is specified here, meaning no analog current or voltage output is provided. The certifications UL-listed C/US and CCC confirm compliance with respective safety standards. The device class Type B (AC, smooth DC, and pulsating DC) ensures detection of all relevant differential current types.
Mounting and Installation
The device is installed in an installation distributor and is designed for mounting in enclosures. The connection terminals allow secure connection of the auxiliary voltage and relay outputs. Adjustments for the measurement range, time delay, and pre-alarm are made via rotary switches, which are protected against unauthorized changes by a tamper-proof transparent cover. Commissioning is carried out according to the instructions in the operating manual, with correct connection to the current transformer and parameter setting being crucial.
Advantages in Operation
The RN5883 provides an information advantage through early fault detection, enabling planned maintenance and reducing downtime. The clear LED display and latching relay outputs ensure reliable fault diagnosis. The universal applicability in AC/DC networks and compatibility with specific current transformers increase flexibility in system planning. Wire break detection and test function enhance system reliability. The UL and CCC certifications ensure use in international markets.