Dold 0066945, EAN: 4030641669454

Dold 0066945 RL9836.11/61 DC24-130V 4-20% 0-30S voltage relay

Dold 0066945 RL9836.11/61 DC24-130V 4-20% 0-30S voltage relay

Lieske Part No. 1002199
Mfg Part No 0066945
EAN-Code 4030641669454
Manufacturer Dold
Here only 148,11 EUR
176,25 EUR incl. VAT

Further information for Dold 0066945 RL9836.11/61 DC24-130V 4-20% 0-30S voltage relay

Technical data
1- / 3-phase1
Auxiliary voltageWithout
Enclosure designDistribution board
Nominal voltage max.DC 250 V
Output contacts1 C/O contact
Width35 mm
TypeRL 9836
Operate delayYes
Variant
Contact equipping1 changeover contact
Hysteresis4 - 20 %
Operating voltageDC 24 - 130 V
Switching delay0 - 30 s
Approvals and MarkingsUL-listed C/US
VariantDe-Energized on trip
The voltage relay RL9836.11/61 from Dold is an industrial device for monitoring DC power supplies. It is used to detect overvoltage, undervoltage, and voltage range exceedances in single-phase systems. The device operates on the rest current principle, where the output relay is energized during normal operation and de-energizes in the event of a fault. The operating voltage range is DC 24 to 130 V, with the switching voltage adjustable within this range. The hysteresis, i.e., the reset range, is adjustable between 4 and 20 % to ensure stable switching behavior during voltage fluctuations. The switching delay can be set from 0 to 30 seconds to enable a time-delayed response to short-term voltage fluctuations.

Applications
This relay is suitable for monitoring DC power supplies in industrial installations, such as in automation systems, machine controls, or emergency power supplies. It can be used to automatically switch to a safety power supply when a fault condition is detected. The application is in single-phase systems, where the monitoring functions can be easily selected via a function selector switch without requiring complex menu structures.

Functions and Equipment in Detail
The device features an output with 1 changeover contact, consisting of one normally closed (NC) and one normally open (NO) contact. The contact rating is designed for an operating voltage of AC/DC 250 V. The contact material is AgNi, ensuring high switching capacity and long service life. The electrical life expectancy is typically 300,000 switching operations at 1 A and AC 230 V. The mechanical life expectancy exceeds 30 million switching operations. Indication is provided via LEDs: a green LED ON" indicates that the operating voltage is present, while red LEDs ">U" and "<U signal overvoltage and undervoltage, respectively. For voltage range monitoring, the range U ± ρU in percent is adjustable, with the hysteresis for returning to the normal state being half of the set ρU value.

Technology Explained Simply
The relay measures the applied DC voltage and compares it with the set switching voltage. If the voltage exceeds or falls below the set threshold, the corresponding LED blinks. After the set switching delay has elapsed, the LED lights up continuously and the output relay de-energizes. When the voltage returns to the desired range, the LED turns off immediately and the relay re-energizes. The response delay is active, meaning the device does not react immediately but includes a short delay to ignore short-term voltage fluctuations. The repeatability accuracy is ±2 %, ensuring high precision in measurement and switching. The temperature influence is ±1 %, ensuring stability under different ambient conditions.

Compatibility and Accessories
The relay is designed for use in installation distributors and has a mounting width of 35 mm, making it suitable for standard control panels. It complies with the standard IEC/EN 60255-1 and is UL-listed C/US, confirming approval for use in the USA and Canada. The maximum rated voltage is DC 250 V. No accessories or additional components are required, as the measurement is performed without auxiliary voltage.

Mounting and Installation
Mounting is done in standard installation distributors with a mounting width of 35 mm. The connection terminals are clearly labeled: L+ for the positive voltage input, L– for the negative voltage input, and contacts 11, 12, and 14 for the changeover contact. The settings for switching voltage, hysteresis, and switching delay are adjusted via rotary dials directly accessible on the device. The functions are selected via a function selector switch, which allows selection between overvoltage, undervoltage, and voltage range monitoring.

Advantages in Operation
By detecting voltage fluctuations early, the relay enables preventive maintenance, avoiding costly damage. The high repeatability accuracy and wide measurement voltage range ensure reliable monitoring. The simple adjustment without menu structures reduces installation time and error sources. The operational safety and high availability of the system are enhanced through continuous monitoring and rapid fault detection. The device is designed for industrial environments and provides a robust and reliable solution for voltage monitoring in DC systems.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002199