Dold 0066944, EAN: 4030641669447

Dold 0066944 RP5898/61 pre-control device for RN5897

Dold 0066944 RP5898/61 pre-control device for RN5897

Lieske Part No. 1153838
Mfg Part No 0066944
EAN-Code 4030641669447
Manufacturer Dold
Here only 264,38 EUR
314,61 EUR incl. VAT

Further information for Dold 0066944 RP5898/61 pre-control device for RN5897

Technical data
Enclosure designDistribution board
Width70 mm
Variant-
TypeRP 5898
Variant
Approvals and MarkingsUL-listed C/US, DNV
The Dold RP5898/61 is a pre-stage device for insulation monitors of the RN 5897 and RN 5893 series, developed to extend the nominal voltage range. It enables monitoring of networks with higher voltages, up to AC 690 V and DC 1000 V, and is used in combination with the corresponding insulation monitors. The device is designed as an installation distributor and has a width of 70 mm, making it suitable for use in standard control panels. The device dimensions are 70 mm (width) × 90 mm (height) × 71 mm (depth), with a net weight of approximately 110 g.

Applications

The pre-stage device RP5898/61 is used in industrial and technical installations where reliable insulation monitoring is required. It is specifically designed for ungrounded AC, DC, and AC/DC networks, particularly in systems with high network capacitance. Typical applications include UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. The extended voltage range enables use in systems that exceed standard voltages, which cannot be monitored without a pre-stage device.

Functions and Equipment in Detail

The device serves as an interface between the insulation monitor and the network to be monitored. It extends the maximum nominal voltages that the insulation monitor can monitor, thus enabling application in higher-voltage systems. The connection is made via the L(+) and L(-) terminals of the insulation monitor, with the pre-stage device adjusting the measurement voltage. The function is part of an overall system consisting of the insulation monitor and the pre-stage device, with the settings and functions of the monitor (such as trip thresholds, alarm functions, display indication) remaining unchanged.

Technology Explained Simply

The pre-stage device operates as an electrical transformer or voltage divider, reducing the high network voltage to a level suitable for the insulation monitor. This allows the monitor to measure insulation resistances in the network without being subjected to the high voltages itself. The measurement is performed between the terminals L(+) / L(-) and PE1 / PE2, and the device can also monitor during de-energized network conditions. The response time is optimized, especially for high network capacitance, to ensure rapid fault detection. Monitoring is carried out in accordance with IEC/EN 61557-8, ensuring standardized and reliable insulation monitoring.

Compatibility and Accessories

The pre-stage device RP5898/61 is specifically designed for insulation monitors RN 5897/010, RN 5897/011, RN 5897/020, RN 5897/021, RN 5897/240, RN 5897/320, RN 5897/321, as well as RN 5893 and RN 5893/100. It extends the maximum nominal voltages to AC 690 V and DC 1000 V. Combination with other pre-stage devices such as RL 5898 or RR 5898 is not intended, as these are designed for different voltage ranges. Use is exclusively in combination with the specified insulation monitors.

Mounting and Installation

The device is mounted in standard control panels, with the width of 70 mm determining the mounting height. Mounting is carried out in the usual manner for installation distributors, connecting the L(+) and L(-) terminals of the insulation monitor to the corresponding terminals of the pre-stage device. The auxiliary voltage is supplied via terminals A1(+) / A2. Installation requires no special tools or additional components, as the device is integrated as a module into the existing system.

Advantages in Operation

Using the pre-stage device RP5898/61 enables flexible expansion of the monitoring capability of insulation monitors. It provides safe and reliable insulation monitoring in higher-voltage networks, ensuring preventive fire protection and system protection. Rapid fault localization through selective earth fault detection, along with adjustable trip thresholds (e.g. pre-alarm and alarm), increases the efficiency of fault detection. Compatibility with existing insulation monitors reduces the need for entirely new systems and allows for step-by-step expansion of monitoring capacity.

Approvals and Markings

The device is UL-listed C/US and carries the DNV approval, confirming compliance with international safety and quality standards. These approvals are relevant for use in various markets, particularly in the USA and Canada, as well as in marine applications. Compliance with these standards ensures the reliability and safety of the device in critical applications.

Functions and Applications

The pre-stage device supports insulation monitoring in complex electrical systems, particularly in installations with high network capacitance. It enables detection of symmetrical and asymmetrical insulation faults and supports rapid fault localization through selective earth fault detection. Its application in ungrounded networks, UPS systems, frequency converters, and battery networks makes it an important component of modern monitoring systems. Adjustable trip thresholds and alarm memory capability increase the flexibility and efficiency of the system.