Dold 0066820, EAN: 4030641668204

Dold 0066820 UH6937.02PS/61 DC24V frequency monitor

Dold 0066820 UH6937.02PS/61 DC24V frequency monitor

Lieske Part No. 1001317
Mfg Part No 0066820
EAN-Code 4030641668204
Manufacturer Dold
Here only 909,76 EUR
1.082,61 EUR incl. VAT

Further information for Dold 0066820 UH6937.02PS/61 DC24V frequency monitor

Technical data
1- / 2-channel2
ApprovalsUL
Cat. / PL acc. to EN ISO 13849-14/e
ClassificationSensorless
ConnectionPluggable cage clamp terminals, Pluggable cage clamp terminals 2-wire, Pluggable screw terminals
Forcibly guided output contacts max.2 NO contacts
Indicator contacts2 Semiconductor monitoring outputs
Measuring motor voltage max.690 V
Nominal voltageDC
SIL CL acc. to IEC/EN 620613
SIL acc. to IEC/EN 620613
Thermal current Ith max.8 A
Width45 mm
TypeUH 6937
Variant
Auxiliary voltageDC 24 V
Contact equipping2 NO contacts
Terminal typepluggable terminal blocks with screw terminals
Approvals and MarkingsUL-listed C/US, TÜV, UKCA, CCC
VariantMax. response value 600 Hz
The frequency monitor UH6937.02PS/61 DC24V from Dold is a safety-relevant monitoring switch for frequency and rotation direction monitoring in industrial drive systems. It is used for monitoring alternating voltages, particularly the output frequency of frequency converters or the rotor frequency of slip ring motors. Another application area is the monitoring of drives in crane systems. The device features a front-mounted display enabling menu-guided parameterization and simplifying adaptation to specific requirements. Settings can be adjusted directly on the device without requiring a PC.

Applications

The frequency monitor is designed for monitoring single-phase and three-phase alternating voltages. It can monitor both frequency and rotation direction, with the option to monitor each parameter separately. Applications include frequency converters up to 1200 Hz, with the specified variant having a maximum response value of 600 Hz. The universal measurement inputs support AC voltages from 8 to 280 V for single-phase and 16 to 690 V for single- and three-phase monitoring. The devices are designed for use in safety applications, with frequency monitoring up to PL e / Category 4 according to EN ISO 13849-1 and SIL 3 according to EN 61508, EN IEC 62061, and EN 61511. Rotation direction monitoring reaches PL d / Category 2 according to EN ISO 13849-1 and SIL 2 according to the mentioned standards.

Functions and Equipment in Detail

The device features two forced-guided make contacts as output contacts, suitable for safe switching operations in safety functions. The contacts are galvanically isolated from the measurement input, auxiliary voltage, and output, ensuring high electrical safety. Two semiconductor alarm outputs enable signal transmission to higher-level control systems. Parameterization is performed via a front-mounted display, which also displays set and actual values for frequency and rotation direction. The response time is short, as frequency is measured by period duration. Adjustable parameters include hysteresis, release delay (0 to 100 s), start-up bypass time (0 to 100 s), and alarm delay (0 to 100 s). For rotation direction monitoring, a tolerance of 5 to 60000 periods is adjustable. Alarm memory or auto-reset can also be configured.

Technology Explained Simply

The operation is based on measuring the input frequency by period duration, enabling fast response. Galvanic isolation between electrical systems (measurement input, auxiliary voltage, output) protects against interference and increases safety. The forced-guided contacts ensure the output is only closed when the input is functioning correctly, which is critical for safety-critical applications. The auxiliary voltage is DC 24 V, which is commonly available in many industrial control systems. The width of 45 mm allows for compact mounting in standard control panels.

Compatibility and Accessories

The frequency monitor is designed for integration into existing drive solutions. Connection technology includes removable spring clamp terminals, 2-wire spring clamp terminals, and removable screw terminals, enabling flexible and quick installation. Plug-in connection blocks facilitate device replacement. The devices are suitable for frequency converters up to 1200 Hz, with the specified variant having a maximum response value of 600 Hz. Certifications include UL-listed C/US, TÜV, UKCA, and CCC, ensuring usability in various markets.

Mounting and Installation

Mounting is performed in standard control panels with a width of 45 mm. Removable terminal blocks with screw terminals allow for quick and secure wiring. Parameterization is done directly on the device via the front-mounted display, eliminating the need for additional software or external devices. Settings can be adjusted at any time, enabling flexible use in various application scenarios.

Operational Advantages

Extensive diagnostic functions reduce downtime, as faults can be quickly identified. The comfortable, menu-guided parameterization shortens commissioning time. Galvanic isolation and forced-guided contacts increase reliability in safety-critical applications. The ability to bypass (mute) frequency and rotation direction monitoring provides additional flexibility in control. Display of set and actual values supports system maintenance and monitoring. The devices are designed for industrial environments and meet safety function requirements up to PL e / Category 4 and SIL 3.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1001317