Dold 0066430, EAN: 4030641664305

Dold 0066430 RL9836.11/61 DC50-250V 4-20% 0-30S voltage relay

Dold 0066430 RL9836.11/61 DC50-250V 4-20% 0-30S voltage relay

Lieske Part No. 1002200
Mfg Part No 0066430
EAN-Code 4030641664305
Manufacturer Dold
Here only 148,11 EUR
176,25 EUR incl. VAT

Further information for Dold 0066430 RL9836.11/61 DC50-250V 4-20% 0-30S voltage relay

Technical data
1- / 3-phase1
Auxiliary voltageWithout
Enclosure designDistribution board
Nominal voltage max.DC 250 V
Output contacts1 C/O contact
Width35 mm
TypeRL 9836
Operate delayYes
Variant
Contact equipping1 changeover contact
Hysteresis4 - 20 %
Operating voltageDC 50 - 250 V
Switching delay0 - 30 s
Approvals and MarkingsUL-listed C/US
VariantDe-Energized on trip
The voltage relay RL9836.11/61 from Dold is a device for monitoring DC power networks in the range of DC 50 to 250 V. It is used for detecting overvoltages, undervoltages, and voltage range exceedances in industrial installations. The device operates on the rest current principle, where the output relay is energized during normal operation and de-energizes in the event of a fault. Function selection is performed via a simple function selector switch, without complex menu structures, enabling quick and intuitive setup.

Applications
This relay is intended for monitoring DC power networks in industrial installations, particularly in systems requiring high operational safety and availability. It is suitable, for example, for monitoring power supplies in automation systems, drives, or emergency power supplies. Upon detection of a fault condition, it can be used to switch to a safety power supply, allowing the system to be shut down without damage or placed in a safe state.

Functions and Features in Detail
The device features an adjustable switching voltage range, an adjustable hysteresis between 4 and 20 %, and an adjustable switching delay from 0 to 30 seconds. The hysteresis ensures that the relay only switches back to the normal state when the voltage is sufficiently stable within the desired range, preventing false alarms and unwanted switching operations. The switching delay prevents short-term voltage fluctuations that could lead to incorrect tripping. Indication is provided via LEDs: a green LED ON" indicates that the operating voltage is present, while red LEDs ">U" (overvoltage) and "<U (undervoltage) signal the respective fault condition.

Technology Explained Simply
The relay measures the applied DC voltage via the connection terminals L+ and L–. The measurement is performed by an integrated measuring circuit that continuously monitors the voltage. If the voltage exceeds or falls below the set switching voltage, the corresponding LED blinks, and after the set delay time, the LED lights up continuously and the output relay de-energizes. When the voltage returns to the desired range, the LED turns off immediately and the relay re-energizes. The contact configuration consists of a changeover contact (1 C/O contact), designed for switching operations with a thermal current load of 5 A. The switching voltage is AC/DC 250 V, and the device complies with the standard IEC/EN 60255-1.

Compatibility and Accessories
The relay is designed for use in single-phase systems and can be mounted in installation distributors. The width is 35 mm, making it suitable for standard distribution boxes. It is UL-listed C/US, confirming approval for use in the USA and Canada. The functions operate independently of an external auxiliary voltage, simplifying integration into existing systems.

Mounting and Installation
Mounting is performed in an installation distributor. The connection terminals are clearly labeled: L+ for the positive voltage input, L– for the negative, and 11, 12, 14 for the changeover contacts. Settings for switching voltage, hysteresis, and delay time are adjusted via rotary controls on the device. The connection terminals are designed for secure connections, and the width of 35 mm allows standard mounting in DIN rail distribution boxes.

Operational Advantages
By detecting voltage deviations early, the relay enables preventive maintenance, preventing costly damage to installations. The high repeatability of ±2 % ensures reliable measurement results. The simple setup without menu navigation reduces installation time and minimizes error sources. Operational safety is ensured by clear LED signaling and the stable switching function of the changeover contact. The device is designed for use in industrial environments where high availability and reliability are required.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002200
qrcode für Dold 0066430 RL9836.11/61 DC50-250V 4-20% 0-30S voltage relay