Further information for Dold 0066429 RL9854.11/61 AC100-300V 4-20% 0-30S voltage relay
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
AC 300 V
Output contacts
1 C/O contact
Width
35 mm
Type
RL 9854
Operate delay
Variant
Contact equipping
1 changeover contact
Hysteresis
4 - 20 %
Operating voltage
AC 100 - 300 V
Switching delay
0 - 30 s
Approvals and Markings
UL-listed C/US
Variant
De-Energized on trip
The voltage relay RL9854.11/61 from Dold is a device for monitoring single-phase AC power networks in the range of AC 100 to 300 V. It is used for continuous monitoring of the supply voltage to detect overvoltage, undervoltage, or voltage range exceedances at an early stage. The device operates on the rest current principle, in which the output relay is energized during normal operation and de-energizes in the event of a fault. The functions can be easily selected via a function selector switch, without requiring complex menu structures. Indication is provided by LED indicators: a green LED indicates that the operating voltage is present, a red LED “>U” signals overvoltage, and a red LED “<U” indicates undervoltage.
Applications
This relay is intended for monitoring AC power networks in industrial and technical installations. It is suitable, for example, for ensuring operational safety in production plants, monitoring power supplies for critical equipment, or controlling switching operations to backup power supplies upon detection of a fault condition. The application is in single-phase systems with 50/60 Hz, with a frequency range of 45 to 65 Hz supported.
Functions and Equipment in Detail
The device features an adjustable switching voltage, which can be set within the range of AC 100 to 300 V depending on requirements. The hysteresis, i.e., the reset range for returning to the normal state, is adjustable between 4 and 20 %. For voltage range monitoring, the range U ± ρU in percent is adjustable, with the hysteresis for returning to the normal state being half of the set ρU value. The switching delay can be set between 0 and 30 seconds to avoid interpreting short voltage fluctuations as faults. The response delay is also integrated to prevent overly rapid reactions to brief voltage fluctuations.
Technology Explained Simply
Measurement is performed via the connected terminals L (phase voltage) and N (neutral conductor). The output relay is equipped with a changeover contact (1 C/O contact), with contact material made of AgNi. The switching voltage is AC 250 V. The nominal frequency is 50/60 Hz, and the nominal consumption is approximately 7 VA. The device is compliant with IEC/EN 60255-1 and designed for use in installation distributors.
Compatibility and Accessories
The relay is designed for mounting in standard installation distributors with a mounting width of 35 mm. It is designed for use in single-phase systems and is not offered for three-phase systems. The functions of overvoltage, undervoltage, and voltage range monitoring are selectable via the integrated function selector switch.
Mounting and Installation
Mounting is performed in an installation distributor, with a standardized mounting width of 35 mm. The connection terminals are clearly labeled: L for phase voltage, N for neutral conductor, and contacts 11, 12, 14 for the changeover contact. Wiring is simple, as no additional auxiliary voltage is required. Settings are made via mechanical rotary controls and a function selector switch, enabling quick and easy commissioning.
Advantages in Operation
By detecting voltage fluctuations early, the relay enables preventive maintenance and thus prevents costly damage. High repeatability and a wide measurement voltage range ensure reliable monitoring. Simple adjustment and clear LED indication facilitate operation and maintenance. The UL approval C/US confirms suitability for use in North America. The device is designed for industrial environments and offers high operational safety.