Further information for Dold 0066092 UG8851.14PS AC/DC24-240V toggle relay
Technical data
Enclosure design
Switch cabinet
Output contacts max.
4 NC contacts, 4 NO contacts
Thermal current Ith max.
6 A
Width
22,5 mm
Type
UG 8851
Suppressor circuit on the coil input
Variant
Contact equipping
4 changeover contacts
Nominal voltage
AC/DC 24 - 240 V
Terminal type
pluggable terminal blocks with screw terminals
The toggle relay UG8851.14PS from Dold is an industrial relay designed for enclosure mounting, intended for operation with a nominal voltage in the range AC/DC 24 to 240 V. It features a contact configuration with 4 changeover contacts and is designed for use in control and regulation technology, where a pulse control is to be converted into a continuous function. The width is 22.5 mm, enabling compact integration into standard enclosures. The device is compliant with IEC/EN 60947-5-1 and features forced-guided contacts according to IEC 61810-3, ensuring reliable status verification of the contact position. Control is achieved via pulse control at terminals A1-A2 (set) and B1-B2 (reset), with coils A2 and B2 internally bridged and sharing the same potential. When both coil systems are energized simultaneously, the first energized system takes priority. Contacts switch within less than 30 ms, with a minimum pulse duration for setting and resetting each exceeding 30 ms. The minimum pause time between two control pulses is over 300 ms. The relay requires no holding power, as it remains in the defined position after the switching pulse. In the event of supply voltage failure, it remains in the last switching position, enabling defined state retention even in fault conditions. Energy efficiency is achieved through low nominal power and absence of holding power, reducing self-heating.
Applications
This toggle relay is suitable for applications where a short pulse control sequence must be converted into a continuous switching function, for example in automation systems, machine control, or safety systems. The ability to retain the switching state even during power failure makes it particularly suitable for critical processes where state loss prevention is required. The forced-guided contacts enable secure state verification, which is advantageous in safety-critical applications.
Functions and Equipment in Detail
The device features removable terminal blocks with screw terminals, enabling quick installation and maintenance. The terminals are coded, supporting error-free installation. Manual operation is performed via a toggle lever, which simultaneously indicates the contact position. Two yellow LEDs indicate energization of coils A1-A2 and B1-B2. The protective circuit at the coil input protects the device against transient voltage spikes. The maximum thermal current rating is 6 A, with the rating applying to the total number of contacts. Switching capacities are AC 15 (3 A / AC 230 V for make contacts, 2 A / AC 230 V for break contacts) and DC 13 (2 A / DC 24 V for make and break contacts). The electrical life is at least 100,000 switching cycles at 1 A and AC 230 V.
Technology Explained Simply
The toggle relay operates on the principle of pulse control: a short current pulse (several milliseconds) is sufficient to bring the relay into a defined switching position. No holding power is required, minimizing power loss. The forced-guided contacts ensure the contact state is mechanically secured and cannot be altered by mechanical irregularities. The protective circuit at the coil input absorbs inductive voltage spikes when the coil is switched off, increasing the relay’s lifespan.
Compatibility and Accessories
The relay is designed for use in enclosures and can be combined with other devices of the same width (22.5 mm). The removable terminal blocks allow for quick replacement of the device without rewiring. The coding of the terminal blocks prevents incorrect connections. Control is via standard control lines, with voltage in the range AC/DC 24 to 240 V. Coils A1-A2 and B1-B2 can be operated with both AC and DC voltage; with DC voltage, terminals A1(+) and B1(+) must be connected to the positive pole.
Mounting and Installation
The relay is mounted in an enclosure, with the width of 22.5 mm determining the mounting height. Terminal blocks are connected via screw terminals, with coding ensuring correct assignment. Manual operation is via the toggle lever, which simultaneously indicates the contact position. The LEDs indicate coil energization. Mounting requires no additional tools, as the terminal blocks are removable.
Operational Advantages
The toggle relay offers high energy efficiency, as no holding power is required. The defined switching position even during power failure increases reliability. Forced-guided contacts enable secure state verification. The compact design and removable terminal blocks simplify installation and maintenance. The protective circuit at the coil input increases the device’s lifespan. Control via short pulses reduces the load on control electronics.
Tamper Protection
The device features a sealable transparent cover providing tamper protection. The cover can be sealed to prevent unauthorized changes to the switching position. This is particularly advantageous in safety-critical applications.
Approvals and Standards
The relay complies with standards IEC/EN 60947-5-1 and IEC 61810-3. Approvals cover requirements for electrical safety, switching function, and contact reliability. Standard IEC 61810-3 specifies requirements for forced-guided contacts, enabling secure state verification.
Switching Capacity and Lifespan
Switching capacity is AC 15 (3 A / AC 230 V for make contacts, 2 A / AC 230 V for break contacts) and DC 13 (2 A / DC 24 V for make and break contacts). Electrical lifespan is at least 100,000 switching cycles at 1 A and AC 230 V. Thermal load capacity is 6 A, with the rating applying to the total number of contacts.
Control and Operation
Control is via pulses at terminals A1-A2 (set) and B1-B2 (reset). Minimum pulse duration is 30 ms, minimum pause time between pulses is 300 ms. Coils A2 and B2 are internally bridged and share the same potential. When both coil systems are energized simultaneously, the first energized system takes priority. Contacts switch within less than 30 ms.
Additional Features
The relay features manual operation via a toggle lever, which simultaneously indicates the contact position. Two yellow LEDs indicate energization of coils A1-A2 and B1-B2. The protective circuit at the coil input protects against transient voltage spikes. Removable terminal blocks allow for quick device replacement. Terminal block coding prevents incorrect connections.
Application Scenarios
The toggle relay is suitable for use in automation technology, machine control, and safety systems. It is ideal for applications where pulse control must be converted into a continuous function. The ability to retain the switching state even during power failure makes it particularly suitable for critical processes. Forced-guided contacts enable secure state verification, which is advantageous in safety-critical applications.