| Technical data |
| Diameter | 24 mm, 35 mm, 70 mm |
| For relay type | IL 5882, SL 5882 |
| Type | ND 5016 |
| Variant |
| Variant | 24 mm inner diameter |
The Dold differential current transformer ND5016/024 is an external measuring transformer for monitoring electrical installations in earthed networks. It is used in conjunction with the differential current monitors IL 5882 and SL 5882 to detect insulation faults early and indicate them to the operator without immediately causing an operational interruption. The transformer is specifically designed for mounting on a DIN rail or by screw fastening and can be installed both horizontally and vertically. It features an inner diameter of 24 mm, making it suitable for cables with a corresponding diameter. The ND 5016 product family also includes variants with 35 mm and 70 mm inner diameters, which are also intended for use with IL 5882 and SL 5882.
Applications
The differential current transformer ND5016/024 is used for continuous monitoring of electrical installations, particularly in industrial and installation environments where early detection of insulation degradation is important. It is employed in earthed networks to detect fault currents arising from insulation faults. The application is carried out in conjunction with the differential current monitors IL 5882 and SL 5882, which evaluate the measurement signals and respond accordingly. The transformers are intended for use in installations where an immediate operational interruption is not required, and a warning is sufficient to initiate maintenance measures.
Functions and Equipment in Detail
The transformer operates on the principle of differential current measurement. All conductors of the circuit to be monitored (excluding the protective earth conductor PE) are passed through the transformer. In a fault-free condition, the sum of all currents is zero, so no voltage is induced in the transformer. However, if an insulation fault occurs, a fault current flows to earth, creating a current difference. This is detected by the transformer and transmitted as a measurement signal to the differential current monitor IL 5882 or SL 5882. The evaluation is performed by the device, which, depending on the setting, issues a pre-warning or alarm. The transformer’s function is independent of frequency within the range of 20 to 2000 Hz, making it suitable for alternating and pulsating direct currents.
Technology Explained Simply
The ND5016/024 is a passive measuring transformer that does not require its own power supply. It functions as a transformer that detects the difference between the currents in the conductors. The measurement is carried out via terminals i and k, which are connected to the differential current monitor. The output power of the transformer is not directly visible but is evaluated by the connected device (IL 5882/SL 5882). The wire break detection ensures that a broken conductor in the transformer circuit is recognized to avoid false alarms. The response time is short, enabling rapid detection of faults. The time delay is adjustable to prevent flickering of the output relay in the case of pulsating fault currents (e.g., from single-phase rectification).
Compatibility and Accessories
The differential current transformer ND5016/024 is specifically developed for use with the differential current monitors IL 5882 and SL 5882. These devices are available in two housing forms: IL 5882 with a 63 mm depth and bottom-mounted terminals, and SL 5882 with a 100 mm depth and top-mounted terminals. Both are designed for mounting in installation and industrial distributors as well as enclosures. The ND 5016 transformers are also available in other diameter variants (35 mm, 70 mm), which are also compatible with IL 5882 and SL 5882. Additionally, other external differential current transformers such as ND 5019 or the hinged current transformer ND 5014 can be used.
Mounting and Installation
The ND5016/024 is mounted either on a DIN rail (DIN 43880) or by screw fastening. DIN rail mounting can be done horizontally or vertically, allowing flexible installation in various enclosures. The terminals i and k of the transformer are connected to the corresponding terminals of the differential current monitor IL 5882 or SL 5882. The conductors of the circuit to be monitored (excluding PE) are passed through the transformer. Correct installation is crucial for functionality, as an incorrect diameter or incomplete conductor routing can lead to false alarms or failure to detect faults.
Operational Advantages
The use of the differential current transformer ND5016/024 enables preventive maintenance of electrical installations. Early detection of insulation faults allows the operator to initiate targeted maintenance measures before serious damage occurs. The status is indicated via LED indicators (green for auxiliary voltage, red for pre-warning and alarm), visually signaling the condition. The use of an external transformer offers installation flexibility, as the transformer can be positioned independently of the monitoring device. Wire break detection increases reliability, as a broken conductor is immediately recognized. The short response time and adjustable delay ensure precise and disturbance-free operation, even with pulsating currents.
Standards and Regulations
The differential current transformer ND5016/024 complies with the requirements of standard IEC/EN 62020. It is designed for alternating and pulsating direct currents, Type A, according to IEC/TR 60755. The frequency range coverage of 20 to 2000 Hz makes it suitable for a wide range of applications. Compliance with these standards ensures safe and reliable operation in industrial and installation environments.