Dold 0065943, EAN: 4030641659431

Dold 0065943 semiconductor contactor AC200-480V AC25A

Dold 0065943 semiconductor contactor AC200-480V AC25A

Lieske Part No. 1001622
Mfg Part No 0065943
EAN-Code 4030641659431
Manufacturer Dold
Here only 197,10 EUR
234,55 EUR incl. VAT

Further information for Dold 0065943 semiconductor contactor AC200-480V AC25A

Technical data
Load current up to40 A
Load voltage up toAC 480 V
Number of poles1-pole
On/Off Input ControlDC
Width45 mm
TypePH 9270
Signalling outputYes
Variant
Auxiliary voltageDC 10 - 12 V
Load currentAC 25 A
Load voltageAC 200 - 480 V
Semiconductor output1-pole
VariantSwitching at zero crossing. Control via A1/A2 with under- and over current monitoring and PNP transistor output with de-energized on trip. With heat sink
The Dold semiconductor contactor PH9270.91/000/01 AC200-480V AC25A is a 1-pole AC semiconductor relay designed for wear-free and noiseless switching as well as continuous monitoring of load circuits in industrial applications. It is particularly suitable for use in machines and plants where high switching frequency and reliability are required, for example in injection moulding machines, extruders, thermoforming and blow-moulding machines, packaging machines, soldering systems, and in the food industry. The device operates on the zero-voltage switching principle, activating or deactivating at each switching operation at a zero crossing of the sinusoidal mains voltage, thereby extending the service life of load components and minimizing electromagnetic interference.

Applications
This semiconductor contactor is intended for use in plants with heating systems, motors, valves, and lighting systems. The integrated load circuit monitoring enables early detection of faults such as load circuit interruption, over- or under-current, missing load voltage, fuse failure, or defects in the power semiconductor. This function is particularly important in applications where failure of the load component could lead to production downtime or damage. Control is performed via terminals A1/A2, with the auxiliary voltage ranging from DC 10 to 12 V.

Functions and Equipment in Detail
The device features a PNP semiconductor alarm output operating on the rest current principle, which is activated upon detection of a fault. Status indication is provided by a dual-color LED: the LED A1/A5,1 cm ( 2 inch ) indicates the status of the control input (yellow = activated, off = not activated), while the LED "Alarm signals the device status (green = no fault, red = fault, off = no auxiliary voltage). The load voltage is AC 200 to 480 V, the load current is AC 25 A, with a maximum load current capacity up to 40 A (AC 51). Control is performed digitally via DC signals.

Technology Explained Simply
The semiconductor contactor is based on two antiparallel-connected thyristors responsible for the switching function. The DCB technology (Direct-Copper-Bonding process) ensures optimal heat dissipation, reducing thermal stress and increasing the device's service life. The integrated heatsink enables efficient heat dissipation and is designed for mounting on a DIN rail, making the device ready for immediate use. The width is 45 mm, allowing compact installation in enclosures. The protection class IP 20 safeguards against direct contact with conductive parts.

Compatibility and Accessories
The device complies with IEC/EN 60947-4-3 standards and is designed for use in industrial control systems. The PLC-compatible alarm output (PNP) allows direct integration into existing control systems. Optionally, a temperature limit switch (normally open) can be inserted into the designated slot on the underside of the device to protect the heatsink in case of overheating (e.g., above 100 °C). For this purpose, a temperature limit switch of type UCHIYA UP62–100 is suitable.

Mounting and Installation
Mounting is done on a DIN rail, with the integrated heatsink enabling direct fixation. Installation must be carried out by a qualified electrician, as the connection terminals (A1/A2, A3+/A2, L1, T1, Alarm) must be securely and correctly connected. Terminal designations are detailed in the datasheet, where A1/A2 represents the control input, A3+/A2 represents the operating voltage and load circuit monitoring, L1 represents the mains connection, T1 represents the load output, and Alarm represents the semiconductor alarm output.

Advantages in Operation
The semiconductor contactor offers high switching capacity with wear-free and noiseless operation. The integrated load circuit monitoring enables rapid fault detection, minimizing downtime. Zero-voltage switching reduces electromagnetic interference and extends the service life of load components. The combination of DCB technology and heatsink ensures reliable heat dissipation, enhancing operational safety. The clear LED indication facilitates diagnosis and maintenance of the device during operation.