Further information for Dold 0065331 insulation monitor LK5894.12/010 UH=DC20-30V
Technical data
Approvals
UL
Enclosure design
Switch cabinet
IMD type
AC, AC/DC, DC
Nominal voltage IT system
AC 0 - 690 V, DC 0 - 690 V
Response value
1 - 250 kΩ
Response value type
Adjustable
Width
90 mm
Type
LK 5894
Connection for indicator
Earth fault indicator
Variant
Alarm value
1 - 250 kOhm
Auxiliary voltage
DC 24 V
Contact equipping
2 x 1 changeover contact
Prewarning value
20 kOhm - 2 MOhm
Approvals and Markings
UL-listed C/US, UKCA
Variant
With wire-break detection at L(+)/L(-)
The insulation monitor LK5894.12/010 from Dold is a device for monitoring insulation in IT systems, designed for mounting in enclosures. It is used for continuous monitoring of ungrounded AC, DC, and mixed AC/DC networks with a rated voltage up to 690 V. The device is part of the VARIMETER IMD family and enables detection of symmetrical and asymmetrical insulation faults. The trip thresholds are adjustable via two rotary switches on the front panel, allowing flexible adaptation to different applications. Indication is provided by an LED bar that visually displays the current insulation resistance, as well as an LED indicating the status measurement circuit active. The auxiliary voltage is DC 24 V, and the device features two changeover contacts for alarm and pre-alarm signals.
Applications
The insulation monitor is universally applicable in various application areas, including UPS systems, networks with frequency converters, battery networks, DC drives, as well as in hybrid and battery-powered vehicles. It is designed for network capacitances up to 1000 μF, making it suitable for systems with high capacitance. Monitoring also occurs when the network is de-energized, ensuring continuous safety. The integrated wire break detection at measurement terminals L(+) and L(-) as well as at protective conductor terminals PE and KE ensures that interruptions in the measurement circuit are immediately detected.
Functions and Equipment in Detail
The pre-alarm threshold is adjustable in the range of 20 kΩ to 2 MΩ, while the alarm threshold can be set between 1 kΩ and 250 kΩ. These values can be easily and clearly adjusted using detent rotary switches with a screwdriver. The insulation resistance is indicated by an LED bar, visually displaying the current status. Additionally, the operating status of the measurement circuit is indicated by an LED. The device features an automatic and manual self-test, which runs for 10 seconds after switching on the auxiliary voltage and checks the functionality of the indicator LEDs.
Technology Explained Simply
The device operates on the principle of active measurement with alternating polarity. During the measurement phase, a test voltage is applied between terminals L(+) / L(-) and PE / KE, with the polarity alternating. When the polarity is positive, the Active LED blinks with a longer ON phase; when negative, with a shorter ON phase. Measurement times are optimized and are typically shorter than with conventional methods. The setting for maximum network capacitance allows adjustment of the response time according to the specific installation. The operating or standby current principle for the output relays can be selected.
Compatibility and Accessories
The device is designed for IT systems with AC, DC, and AC/DC networks and complies with the standard IEC/EN 61557-8. It is designed for mounting in enclosures and has a width of 90 mm. Certifications include UL-listed C/US and UKCA. The connection terminals are clearly labeled: A1+ and A2 for DC auxiliary voltage, L(+) and L(-) for the measurement circuit, KE and PE for the protective conductor, G and R for the control input (memory or hysteresis behavior), G and T for the external test input. Relay contacts 11, 12, 14 are for the alarm signaling relay, and 21, 22, 24 for the pre-alarm signaling relay.
Mounting and Installation
Mounting is done in an enclosure. Terminals L(+) and L(-) are connected to the network to be monitored, while PE and KE are connected to the protective conductor system via separate conductors. The auxiliary voltage is supplied via A1+ and A2. Settings are adjusted using the rotary switches on the front panel. Measurement values are displayed via the LED bar. The integrated wire break detection ensures that interruptions in the measurement circuit are immediately detected.
Advantages in Operation
The insulation monitor provides preventive fire and system protection through early detection of insulation faults. Selective earth fault detection according to L+ and L- enables quick fault localization. Simple adjustment via rotary switches and visual indication via LEDs simplify operation. Monitoring even when the network is de-energized and integrated wire break detection increase reliability. No additional pre-stage device is required, simplifying installation. Measurement times are optimized, and the device is suitable for network capacitances up to 1000 μF, ensuring broad applicability.