| Technical data |
| Approvals | UL |
| Enclosure design | Distribution board |
| Output contacts | 1 C/O contact |
| Time function(s) | Fleeting on make |
| Width | 17,5 mm |
| Type | RK 7815 |
| Variant |
| Contact equipping | 1 changeover contact delayed |
| Nominal voltage | AC 110 - 127 V + AC/DC 24 V |
| Time range | 1 - 10 s |
| Approvals and Markings | UL-listed C/US |
| Variant | Fleeting action |
The Dold RK7815.71/61 AC110-127V+AC/DC24V is an
on-delay time relay of the RK series, developed for implementing time-dependent control functions in industrial applications and building automation. The device features a compact distributor housing and is designed for use in installation distributor boxes. It provides a
1-changeover contact configuration, which switches with delay, and is rated for a nominal voltage of AC 110–127 V as well as AC/DC 24 V. The time function is set within the range of 1 to 10 seconds, with stepless adjustment via a relative scale with a ratio of 1:10. The repeat accuracy is ≤ 0.5 % of the set time range end value plus 10 ms, ensuring high precision in repeated switching operations.
Applications
This relay is suitable for applications requiring a short, delayed switching function, for example, to delay the start-up of motors, pumps, or lighting systems. The function as an
on-delay time relay means that the contact switches with delay after voltage is applied and immediately returns to its initial position after voltage is removed. This is particularly useful in systems where immediate shutdown after power failure is required, while start-up is to be delayed. The width of 17.5 mm allows for compact mounting in standard distributor boxes.
Functions and Equipment in Detail
The device features an LED indicator showing the state of the output relay – it lights up when the contact 15–18 is closed. Power supply is via two inputs: AC voltage (110–127 V) is connected at terminals A1–A2, while AC/DC voltage (24 V) is supplied at A3–A2. The drop-out voltage is approximately 40 V (A1–A2) for AC 50 Hz and approximately 5 V (A3–A2) for DC. The nominal power consumption is approximately 1 VA for AC 24 V. The reset time is < 100 ms, enabling rapid response after a switching-off event.
Technology Explained Simply
The time function is based on a mechanical time relay with stepless adjustment. The time delay is generated by a mechanical clockwork function activated upon voltage application. The delay occurs only during switching on (on-delay), while the contact returns immediately upon switching off. Adjustment is made via a rotary control on the front of the device, scaled on a relative scale with a ratio of 1:10. The temperature dependence is 0.25 % per Kelvin, ensuring stable operation over a wide temperature range. The voltage influence limit is ≤ 1 %, indicating low dependency on voltage fluctuations.
Compatibility and Accessories
The relay is part of the RK series, which includes various time functions, such as delayed-action relays (RK 7813, RK 7814), time relays (RK 7815), and blinking relays (RK 7816). The RK series complies with IEC/EN 61812-1 standards. The voltage version AC 110–127 V + AC/DC 24 V is specifically designed for applications in regions with this voltage specification. Devices in the RK series are designed for mounting in installation distributor boxes and offer a uniform width of 17.5 mm.
Mounting and Installation
Mounting is carried out in standard installation distributor boxes. The terminals are clearly labeled: A1–A2 for AC voltage (110–127 V), A3–A2 for AC/DC voltage (24 V), and 15–16–18 for the changeover contact. The LED indicator is directly visible on the device. Adjustment of the delay time is performed via the rotary control on the front. The reset time is so short that the device is operational again within 100 ms after a switching-off event.
Advantages in Operation
The relay provides reliable, precise time delay in the range of 1 to 10 seconds. The combination of two voltage inputs enables flexible use in systems with different voltage sources. The LED indicator facilitates diagnostics during operation. The short reset time and high repeat accuracy make the device suitable for applications requiring fast and precise response. Compliance with IEC/EN 61812-1 and UL approval (C/US) ensure adherence to international safety standards.