| Technical data |
| 1- / 2-channel | 1, 2 |
| Approvals | UL |
| Cat. / PL acc. to EN ISO 13849-1 | 4/e |
| Connection | Pluggable cage clamp terminals, Pluggable cage clamp terminals 2-wire, Pluggable screw terminals |
| Output contacts max. | 1 NC contact, 7 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 8 A |
| Width | 22,5 mm |
| Type | UG 6929 |
| Variant |
| Contact equipping | 5 NO contacts, 1 NC contact for feedback circuit |
| Nominal voltage | AC/DC 24 V |
| Terminal type | pluggable terminal blocks with screw terminals |
| Approvals and Markings | UL-listed C/US, TÜV |
| Variant | For 2-channel connections |
The Dold expansion module UG6929.60PS/100/61 AC/DC24V is a safety relay module for use in industrial control systems, particularly for safe contact multiplication and amplification of safety modules. It is used in installations where multiple safety circuits are required than a single safety module can provide. The module enables actuation even via safety-oriented semiconductor outputs, such as with BWS or emergency stop switches, and provides reliable, forced-guided contact operation. The operational status indicator supports visual monitoring of the module during operation.
Applications
The module is intended for applications in industrial automation, particularly in systems with increased safety requirements. It is frequently used in combustion systems, as it meets the requirements of EN 50156-1. The module is used in 1- or 2-channel wiring configurations, with the 2-channel variant enabling redundant safety functions. Application areas also include machine controls requiring safe signal transmission and amplification.
Functions and Equipment in Detail
The UG6929.60PS/100/61 AC/DC24V features a contact configuration with 5 normally closed contacts and 1 normally open contact, specifically designated for the feedback circuit. This configuration enables safe monitoring of signal transmission and amplification of contact signals. The maximum number of output contacts is 7 normally closed contacts or 6 normally closed contacts with 1 normally open contact, with the normally open contact serving the feedback circuit. The contacts are forced-guided, meaning they are mechanically designed so that opening one contact is always linked with closing another — an important feature for safety functions.
Technology Explained Simply
The module operates at a rated voltage of AC/DC 24 V, making it suitable for use in standard industrial control systems. The maximum thermal current rating is 8 A, describing the contact load capacity under continuous operation. The width of 22.5 mm allows for compact mounting in standard control panels. The connection technology includes removable terminal blocks with screw terminals, enabling quick replacement of the module. Alternatively, spring-cage terminals are available, providing fast and secure connections.
Compatibility and Accessories
The module is designed for use in conjunction with suitable switching devices, particularly in systems utilizing safety-oriented semiconductor outputs. It is suitable for 1- and 2-channel wiring configurations, with the 2-channel variant offering a higher safety level. Certifications include UL-listed C/US and TÜV, confirming compliance with international safety standards. The safety categories correspond to Category 4 and Performance Level e according to EN ISO 13849-1, as well as Safety Integrity Level (SIL) 3 according to IEC/EN 62061. These markings confirm suitability for applications with high safety requirements.
Mounting and Installation
Mounting is performed in standard control panels with a width of 22.5 mm. The removable terminal blocks allow for easy and secure connection of wiring. Screw terminals provide a secure connection, while spring-cage terminals enable quick installation without tools. The operational status indicator facilitates visual inspection of the module during operation. Installation is carried out according to the manufacturer’s technical instructions, with correct wiring of safety circuits and the feedback circuit being critical.
Advantages in Operation
The module provides safe and reliable contact multiplication, increasing the number of available safety outputs. The forced-guided contacts ensure high safety, as there is a mechanical interconnection between contacts. The operational status indicator enables quick fault detection. The use of removable terminal blocks simplifies replacement and maintenance. Certifications according to UL, TÜV, and international safety standards confirm suitability for critical industrial applications.