Dold 0065245, EAN: 4030641652456

Dold 0065245 current relay AC30-300mA Tv=0-20s

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0065245 current relay AC30-300mA Tv=0-20s

Lieske Part No. 1331533
Mfg Part No 0065245
EAN-Code 4030641652456
Manufacturer Dold
Here only 291,36 EUR
346,72 EUR incl. VAT

Further information for Dold 0065245 current relay AC30-300mA Tv=0-20s

Technical data
1- / 3-phase1
Enclosure designSwitch cabinet
Output contacts2 C/O contacts
Width22,5 mm
TypeMK 9053N
Operate delayYes
Variant
Auxiliary voltageAC/DC 24 - 80 V
Contact equipping2 changeover contacts
Measuring rangeAC 30 - 300 mA
Start up delay0,1 - 20 s
Switching delay0 - 20 s
Terminal typescrew terminal fixed
Approvals and MarkingsCCC
VariantUndercurrent relay, de-energized on trip
The current relay MK9053N.12/012 AC30-300mA Tv=0-20s from Dold is an undercurrent relay operating on the rest current principle, designed for monitoring single-phase DC or AC networks. It is used for continuous monitoring of the current consumption of electrical loads to react promptly to deviations or interruptions in current flow. Device settings are adjusted via rotary switches on the front panel, enabling simple and user-friendly configuration. The device is intended for use in enclosures and has a width of 22.5 mm, fitting into standard 35 mm mounting rails.

Applications
This relay is suitable for industrial applications as well as railway applications where reliable current monitoring is required. It monitors the current consumption of motors, transformers, or other electrical loads to prevent failures caused by insufficient current or interruptions. Early detection of faults enables preventive maintenance and increases the operational safety of the system.

Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits. The measurement ranges are fixed at AC 30 to 300 mA, with the devices calibrated for sinusoidal AC currents in RMS value. Measurement is performed using the arithmetic mean of the rectified measured current. The auxiliary voltage is AC/DC 24 to 80 V, allowing flexible integration into existing control systems. The start-up bypass is adjustable from 0.1 to 20 seconds and prevents false alarms during motor start-up, which may involve temporarily increased currents.

Technology Explained Simply
The switching delay (Tv) is 0 to 20 seconds and delays the relay’s switching action after exceeding a threshold. In undercurrent relays, this delay acts after falling below the hysteresis value, enabling controlled response to short-term current drops. Galvanic isolation between the measurement circuit and auxiliary circuit ensures high safety and prevents interference in the control circuit. The LED indicator shows operational readiness (green LED) and contact position (yellow LED), facilitating diagnostics during operation.

Compatibility and Accessories
The relay complies with IEC/EN 60255-1 and IEC/EN 60947-1 standards. It is designed for frequencies from 50 to 5000 Hz, making it suitable for high-frequency applications. The terminal type is a fixed screw terminal, ensuring a secure and durable connection. The devices are designed for maximum overload capacity, with the maximum permissible continuous current for the AC 30–300 mA measurement range being 2 A. The maximum current load for 3 seconds is 2.5 A, after which the devices are switched off after 100 seconds.

Mounting and Installation
Mounting is done in enclosures using mounting rails. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, i/k for current input, and contacts 11/12/14 and 21/22/24 for the two changeover contacts. Settings are adjusted via rotary switches on the front panel, allowing both the pickup value and the drop-out value to be set via hysteresis. The devices are designed for use in industrial environments and meet requirements for reliability and longevity.

Operational Advantages
Precise and reliable current monitoring enables quick fault localization and preventive maintenance. The LED indicator supports operational monitoring, and the switching delay and start-up bypass prevent unnecessary shutdowns. Galvanic isolation between the measurement and auxiliary circuits enhances safety and prevents interference. The width of 22.5 mm allows compact installation in existing enclosures.

Approvals and Markings
The device carries the CCC approval, confirming compliance with applicable safety and quality standards. The devices are suitable for use in industrial plants and railway applications, with standards compliance ensuring safe and reliable operation.