Further information for Dold 0065217 insulation monitor LK5895.12/010 UH=DC20-30V
Technical data
Approvals
UL
Classification
For photovoltaic systems
Enclosure design
Switch cabinet
IMD type
AC, AC/DC, DC
Nominal voltage IT system
AC 0 - 1000 V, DC 0 - 1000 V
Response value
1 - 250 kΩ
Response value type
Adjustable
Width
90 mm
Type
LK 5895
Earth fault indicator
Variant
Alarm value
1 - 250 kOhm
Auxiliary voltage
DC 24 V
Contact equipping
2 x 1 changeover contact
Prewarning value
20 kOhm - 2 MOhm
Approvals and Markings
UL-listed C/US, UKCA
Variant
With wire-break detection at L(+)/L(-). Without analog output
The insulation monitor LK5895.12/010 UH=DC20-30V from Dold is a device for monitoring insulation in IT systems, particularly in ungrounded AC, DC, and mixed AC/DC networks with a nominal voltage up to 1000 V. The device belongs to the VARIMETER IMD family and is specifically developed for use in photovoltaic systems, including those with thin-film technology. It enables continuous monitoring of insulation resistance and detects both symmetrical and asymmetrical insulation faults. The setting of trigger values is done via two ratchet rotary switches on the device front, allowing user-friendly and precise configuration.
Applications
The insulation monitor is universally applicable in various applications, including photovoltaic systems, UPS systems, networks with frequency converters, battery networks, DC drives, as well as in hybrid and battery-powered vehicles. It is designed for network capacitances up to 3000 μF, making it suitable for systems with high capacitances. Monitoring also occurs when the network is de-energized, ensuring continuous safety.
Functions and Equipment in Detail
The device features two changeover contacts – one for pre-alarm and one for alarm. The pre-alarm threshold is adjustable between 20 kΩ and 2 MΩ, and the alarm threshold between 1 kΩ and 250 kΩ. The current insulation resistance is displayed via an LED bar, visually indicating the status. Additionally, the measurement circuit active indicator is shown to signal the operating state. The measurement circuits can be deactivated via control terminals, for example, during network coupling. The wire break detection function on L(+) and L(−) provides additional safety by detecting interruptions in the measurement circuit.
Technology Explained Simply
Insulation monitoring is performed according to IEC/EN 61557-8, ensuring a standardized and reliable measurement method. The device operates with either a working or resting current principle for the output relays, with selection possible depending on the application. The response time can be shortened by setting the maximum network capacitance. An automatic and manual device self-test ensures functional verification. The auxiliary voltage is DC 24 V, and the device is designed for use in enclosures with a width of 90 mm.
Compatibility and Accessories
The device is designed for IT systems with AC and DC voltages up to 1000 V. It is equipped with an LED indicator for earth fault, visually signaling the system status. External test and reset buttons can be connected to extend operation. Certifications include UL-listed C/US and UKCA, enabling use in various markets.
Mounting and Installation
Mounting is done in enclosures. The connection terminals are clearly labeled: A1+ and A2 for DC auxiliary voltage, L(+) and L(−) for the measurement circuit, KE and PE for the protective conductor, and G, R, T, and HM for control inputs. Settings are adjusted using a screwdriver via the rotary switches on the front. Device functions can be read via the LEDs and relay outputs.
Operational Advantages
The insulation monitor provides preventive fire and system protection through early detection of insulation faults. Selective earth fault detection according to L(+) and L(−) enables quick fault localization. Simple adjustment and clear display reduce maintenance time. Measurement also occurs when the network is de-energized, ensuring continuous monitoring. The integrated wire break detection increases system reliability.
Certifications and Markings
The device is UL-listed C/US and UKCA-certified, confirming compliance with applicable safety and quality standards in the USA and the United Kingdom. The certifications are valid for use in IT systems with AC and DC voltages up to 1000 V.
Enclosure Design and Mounting
The device is designed for use in enclosures. The width is 90 mm, enabling compact mounting in standard enclosures. The front features adjustment rotary switches and an LED display, allowing direct operation at the device.
Display and Status Monitoring
The LED bar displays the current insulation resistance, with the colors and positions of the LEDs visually indicating the status. Additionally, the measurement circuit active indicator is shown to signal the operating state. The LEDs for pre-alarm and alarm light up when the respective thresholds are reached, directly informing the operator.
Self-Test and Diagnostics
The device performs an internal self-test after auxiliary voltage is applied, lasting 10 seconds. During this time, the LEDs in the display bar are activated sequentially to check functionality. A manual self-test is also possible to verify device function at any time.
Control and Operating Modes
Control is done via terminals G, R, T, and HM. The combination of G and R determines the memory behavior (manual or automatic reset). Terminals G and T allow connection of external test buttons, while G and HM enable deactivation of the measurement circuit. The output relays operate in either working or resting current mode, depending on the setting.
Application in Photovoltaic Systems
The insulation monitor is specifically developed for photovoltaic systems, including those with thin-film technology. Its ability to function even with high network capacitances makes it particularly suitable for modern PV systems, which often have high capacitances. Continuous monitoring and fast fault detection contribute to the safety and reliability of the installation.