Further information for Dold 0065158 MK9300N.11PS/022 time relay 3AC24-400V
Technical data
1- / 3-phase
1, 3
Enclosure design
Switch cabinet
Measuring range max.
400 V
Output contacts
1 C/O contact
Standard measuring range
3 AC 24 - 400 V
Width
22,5 mm
Type
MK 9300N
Operate delay
Variant
Auxiliary voltage
DC 24 V
Contact equipping
1 changeover contact
Measuring current
AC 12 A
Measuring voltage
3AC 24 - 400 V
Terminal type
pluggable terminal blocks with screw terminals
Approvals and Markings
DNV
The Dold MK9300N.11PS/022 is a multifunctional measuring relay of the VARIMETER PRO series, designed for electrical monitoring in industrial installations. It enables simultaneous monitoring of up to nine different electrical parameters, including voltage, current, frequency, phase sequence, phase failure, asymmetry, active, reactive and apparent power, as well as the phase angle cos φ. The device is designed for use in enclosures and is suitable for monitoring 1- and 3-phase networks. The auxiliary voltage is DC 24 V, allowing integration into systems with direct current supply. The width of 22.5 mm enables space-saving installation in standard control panels.
Applications
This measuring relay is intended for use in industrial and technical installations, particularly for monitoring motors, transformers, emergency power supplies, and mobile consumers. It can be used for voltage-dependent switching functions in case of over- or undervoltage to prevent damage to connected devices. The phase sequence and asymmetry monitoring functions make it especially suitable for motor protection, while frequency monitoring is beneficial in installations with frequency converters. The devices are also suitable for monitoring 1-phase networks, where terminals L2 and L3 must be bridged.
Functions and Equipment in Detail
The device features a relay output with 1 changeover contact, which can be used to control auxiliary contacts or warning signals. The monitoring functions are independently adjustable, allowing different threshold values to be set for voltage, current, or frequency. The response delay ensures that short-term fluctuations do not trigger the relay, which is important during startup or transient disturbances. The hysteresis is adjustable between 0.2 and 50 % of the response value to minimize false alarms. A fault memory enables diagnosis of previous triggering events.
Technology Explained Simply
Measurement is performed via terminals L1, L2, and L3, assuming a symmetrical load on all three phases, as is typical for motor loads. The measurement voltage range is 3 AC 24 to 400 V, and measurement is also possible in single-phase networks. The measurement current limit is AC 12 A. Display is via an LCD screen showing current measurement values such as voltage, current, or frequency. The LED signal lamp indicates the operating status: green for present auxiliary voltage, red flashing for overload in the current path, and orange for input mode. The startup bypass time prevents changes occurring shortly after auxiliary voltage is applied from affecting the relay output.
Compatibility and Accessories
The device is equipped with removable terminal blocks with screw terminals. These allow for easy installation and maintenance. Terminal blocks are also optionally available with spring clamp terminals, facilitating cable connection. The devices comply with the standard EN 60255-1 and are certified with DNV approval, confirming their suitability for use in marine and industrial environments.
Mounting and Installation
Mounting is done in an enclosure, with the width of 22.5 mm enabling compact placement. Connections for auxiliary voltage (A1/A2) and measured values (L1/L2/L3) are clearly marked. Parameterization is performed via a menu structure that allows intuitive operation. Settings can be adjusted directly on the device, eliminating the need for external programming.
Advantages in Operation
Simultaneous monitoring of multiple parameters enables the device to respond early to potential disturbances, allowing preventive maintenance. Reduced wiring and compact design lower installation costs. Clear display of measurement values and differentiated fault messages facilitate diagnosis and maintenance. The reliability of the device contributes to the operational safety and availability of the entire installation.