Dold 0065131, EAN: 4030641651312

Dold 0065131 insulation monitor LK5896.13/100 UH=DC20-30V

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0065131 insulation monitor LK5896.13/100 UH=DC20-30V

Lieske Part No. 1338917
Mfg Part No 0065131
EAN-Code 4030641651312
Manufacturer Dold
Here only 2.568,05 EUR
3.055,98 EUR incl. VAT

Further information for Dold 0065131 insulation monitor LK5896.13/100 UH=DC20-30V

Technical data
ApprovalsUL
ClassificationFor photovoltaic systems
Enclosure designSwitch cabinet
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 1000 V, DC 0 - 1000 V
Response value1 - 250 kΩ
Response value typeAdjustable
Width90 mm
TypeLK 5896
Connection for indicatorYes
Earth fault indicatorYes
Variant
Alarm value1 - 250 kOhm
Auxiliary voltageDC 24 V
Contact equipping3 x 1 changeover contact
Prewarning value20 kOhm - 2 MOhm
Approvals and MarkingsUL-listed C/US, UKCA
VariantWith wire-break detection at L(+)/L(-). With analog output. With auxiliary measuring circuit
The insulation monitor LK5896.13/100 UH=DC20-30V from Dold is a device for monitoring insulation quality in IT systems, particularly in ungrounded AC, DC, and mixed AC/DC networks with a nominal voltage up to 1000 V. The device belongs to the VARIMETER IMD family and is specifically designed for use in photovoltaic systems, including those with thin-film technology, as well as in systems with frequency converters, battery networks, and DC drives. It enables continuous monitoring of insulation resistance and responds to earth fault conditions, with detection of both symmetrical and asymmetrical faults being possible. Device settings are adjusted via detent rotary switches on the front panel, ensuring simple and clear operation.

Applications

The device is universally applicable in various applications, including photovoltaic systems, UPS systems, networks with frequency converters, battery networks, and hybrid or battery-powered vehicles. It is designed for network capacitances up to 3000 μF, making it suitable for systems with high capacitance. Insulation monitoring is performed in accordance with standard IEC/EN 61557-8, ensuring reliability and compatibility with international standards. Monitoring is also possible in de-energized networks, providing continuous safety even during standstill.

Functions and Equipment in Detail

The LK5896 features three changeover contacts: one for pre-alarm, one for alarm, and a third for signaling wire break and device faults. The pre-alarm threshold is adjustable between 20 kΩ and 2 MΩ, while the alarm value ranges from 1 kΩ to 250 kΩ. Settings are adjusted via rotary switches, with the maximum network capacitance also adjustable to reduce response time. The measurement circuits can be deactivated via control terminals, for example during network coupling. An integrated self-test allows for automatic and manual testing of the device, with alarm memory being selectable. External test and reset buttons can be connected to extend operation.

Technology Explained Simply

Insulation monitoring is performed via a main measurement circuit connected to terminals L(+) and L(-), with an additional measurement circuit at terminals U and V enabling monitoring of a second network section, for example an inverter in the switched-off state. The measurement circuits are equipped with wire break detection to identify interruption of the measurement line. The current insulation resistance is displayed via an LED chain, providing visual indication of the status. An analog output delivers the insulation resistance value as a voltage signal (0...10 V or 2...10 V) and current signal (0...20 mA or 4...20 mA), which can be connected to higher-level controls or external display units.

Compatibility and Accessories

The device is designed for IT systems with AC and DC voltages up to 1000 V and can be used in mixed AC/DC networks. The auxiliary voltage is DC 24 V. The width is 90 mm, enabling installation in standard enclosures. Approvals include UL-listed C/US and UKCA, allowing use in various markets. Device functions are designed for integration into larger monitoring systems, with the trigger output usable for insulation fault detection systems.

Mounting and Installation

Mounting is performed in an enclosure, with the 90 mm width meeting standard mounting conditions. Connections are clearly labeled: A1+ and A2 for DC auxiliary voltage, L(+) and L(-) for the main measurement circuit, U and V for the additional measurement circuit, KE and PE for the protective conductor. Control terminals G, R, T, HM, and ZM allow configuration of memory behavior, external test input, and deactivation of measurement circuits. Connection options for the analog output (XA, GA, IA, UA) and relay contacts (11-14, 21-24, 31-34) are clearly defined, enabling flexible integration into existing systems.

Operational Advantages

Operation of the LK5896 provides preventive protection against fires and system faults through early detection of insulation defects. Selective earth fault detection via L(+) and L(-) enables rapid fault localization. Optimized measurement times are typically shorter than with conventional methods, increasing responsiveness. The ability to monitor insulation resistance even in de-energized networks enhances safety during operational pauses. Integrated wire break detection and indication of active measurement circuits support maintenance and diagnostics. Simple adjustment via rotary switches and visual LED indication reduce operational complexity.