| Technical data |
| 1- / 2-channel | 1, 2 |
| Approvals | UL |
| Cat. / PL acc. to EN ISO 13849-1 | 4/e |
| Connection | Pluggable cage clamp terminals, Pluggable screw terminals, Screw terminals |
| Output contacts max. | 4 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 5 A |
| Width | 22,5 mm |
| Type | LG 5924 |
| Variant |
| Contact equipping | 2 NO contacts |
| Nominal voltage | AC 230 V 50/60 Hz |
| Terminal type | screw terminals fixed |
| Approvals and Markings | UL-listed C/US, TÜV, UKCA, CCC |
The emergency stop module LG5924.02/61 AC50/60HZ 230V from Dold is a safety relay for use in industrial plants, ensuring the protection of personnel and machinery through safety-oriented enabling and interruption of a safety circuit. It is designed for applications requiring high safety integrity and complies with standards for safety functions in automation technology. The device is available as a 1- or 2-channel variant and offers a width of 22.5 mm, making it suitable for standard DIN control panels.
Applications
This module is used in safety-critical systems, particularly in combustion systems according to EN 50156-1, where safe control of operating states is required. It serves as a central component in emergency stop systems that safely shut down operations in case of faults or hazardous situations. The application is in industrial environments where compliance with safety standards such as EN ISO 13849-1 and IEC/EN 62061 is mandatory.
Functions and Equipment in Detail
The device features two normally open (NO) contacts as standard, with up to four NO contacts per device being realizable. The contacts are rated for a thermal current Ith of up to 5 A. The nominal voltage is AC 230 V at 50/60 Hz. Galvanic isolation in the circuit ensures safe electrical separation between control and load circuits. Status indication is provided by LEDs, signaling the operating state and the states of channels 1 and 2. Integrated short-circuit detection between terminal Y1 and ground enables early recognition of faults in the connection area.
Technology Explained Simply
The module operates on the principle of a safety relay, which only activates the output when all specified safety conditions are met. The functions are designed so that in the event of a failure or disturbance in the system, the safety state is automatically initiated. Wire connections can be made with stranded conductors up to 2 x 1.5 mm² with ferrules and plastic collars, or with solid conductors up to 2 x 2.5 mm² according to DIN 46 228-1/-2/-3/-4. The terminal type is fixed screw terminals, with removable spring terminals or removable screw terminals available as optional features.
Compatibility and Accessories
The device is designed for 1- or 2-channel wiring and can be used in safety systems with corresponding architecture. Certifications include UL-listed C/US, TÜV, UKCA, and CCC, enabling use in various markets. Optional plug-in terminal blocks are available, allowing for quick device replacement. Compatibility with other safety components is ensured through the mentioned standards and certifications.
Mounting and Installation
Mounting is performed in standard DIN control panels with a width of 22.5 mm. The connection terminals are designed for the specified conductor cross-sections, with the use of ferrules and plastic collars for stranded wires recommended. Installation must follow the manufacturer’s technical instructions, ensuring correct wiring and compliance with safety regulations.
Advantages in Operation
The module offers high safety integrity with Performance Level (PL) e and Category 4 according to EN ISO 13849-1, as well as SIL 3 according to IEC/EN 62061. The integrated short-circuit detection and LED indicators enhance diagnostic capability during operation. Galvanic isolation and robust construction ensure reliable performance in industrial environments. The option for 1- or 2-channel wiring allows flexible adaptation to different requirements.