| Technical data |
| Approvals | UL, UL-Recognized |
| Load current up to | 88 A |
| Load voltage up to | AC 600 V |
| Number of poles | 1-pole |
| On/Off Input Control | AC, AC/DC, DC |
| Width | 22,5 mm |
| Type | PK 9260 |
| Variant |
| Control voltage | DC 4 - 32 V |
| Load current | AC 40 A |
| Load voltage | AC 48 - 480 V |
| Semiconductor output | 1-pole |
| Approvals and Markings | UL-listed C/US |
| Variant | Switching at zero crossing. M4 flat terminal. With heat sink |
The Dold semiconductor relay PK9260.91/000/05 AC48-480V AC40A is a 1-pole AC semiconductor relay for use in industrial plants. It is designed as a zero-voltage switch for resistive loads and is particularly suitable for applications such as heating systems, cooling systems, and lighting. The device is controlled by a control voltage in the range DC 4–32 V and switches the load voltage of AC 48–480 V with a load current of up to 40 A. Switching occurs at the next zero crossing of the sinusoidal supply voltage when turning on and at the next zero crossing of the load current when turning off, ensuring minimal network interference and long service life. The LED indicator signals the status of the control input.
Applications
This semiconductor relay is suitable for use in machines and plants in the plastics and rubber industry, packaging machines, soldering systems, and in the food industry. It is frequently used in injection moulding machines and other plants where a wear-free, noiseless, and vibration-resistant switching function is required. The zero-voltage switching is particularly advantageous for resistive loads such as heaters or resistance heaters, as it switches the power supply without voltage spikes.
Functions and equipment in detail
The device features two antiparallel-connected thyristors that perform the switching function. The DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, reducing thermal stress and increasing service life. The connection type is designed as an M4 flat terminal, enabling a secure and quick connection. The width is 22.5 mm, minimizing space requirements in the enclosure. The device is equipped with a heatsink that can be snap-mounted onto a DIN rail to ensure optimal heat dissipation.
Technology explained simply
Zero-voltage switching means that the relay does not switch abruptly, but at the next zero crossing of the voltage. This prevents voltage spikes and reduces electromagnetic interference (EMV). The control voltage is connected via a digital input (AC, AC/DC, DC). The turn-on delay is maximum 1.0 ms plus half a cycle of the supply voltage, and the turn-off delay is maximum 1.0 ms plus half a cycle. The peak blocking voltage is up to 1600 V, and the insulation voltage is 4000 V, ensuring high electrical safety.
Compatibility and accessories
The semiconductor relay complies with IEC/EN 62314 as well as IEC/EN 60947-4-2 and -4-3. It is UL-listed C/US and UL-Recognized, confirming approval for use in the USA and Canada. The load voltage can reach up to AC 600 V, and the load current up to 88 A (AC-51), with the specified variant being 40 A at AC 48–480 V. Control is via AC, AC/DC, or DC. Mounting is either on existing cooling surfaces with two screws or with the integrated heatsink on a DIN rail.
Mounting and installation
Mounting is either directly onto a cooling surface with two screws or using the integrated heatsink on a DIN rail. When mounting multiple relays side by side, sufficient cooling and ventilation must be ensured to avoid overheating. The terminal designation is A1(+)/A2 for the control input, L1 for the supply connection, and T1 for the load output. During installation, ensure that environmental conditions and load do not impair cooling.
Advantages in operation
The device is characterized by high switching frequency, long service life, noiseless and vibration-free operation. The space-saving design with a width of 22.5 mm and easy mounting on DIN rails or cooling surfaces facilitates integration into existing enclosures. The LED indicator allows for quick status checking. The DCB technology and heatsink ensure efficient heat dissipation, increasing operational reliability. Zero-voltage switching reduces EMV interference and protects connected loads from voltage spikes.