Further information for Dold 0064848 overcurrent relay SP9270.12CT AC220-240V
Technical data
1- / 3-phase
3
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
70 mm
Type
SP 9270CT
Operate delay
Variant
Auxiliary voltage
AC 220 - 240 V
Contact equipping
2 changeover contacts
Measuring range
5 - 50 A
Time delay
0,1 - 20 s
Variant
3-phase current relay with built in CT. De-energized on trip
The Dold overcurrent relay SP9270.12CT is a 3-phase current relay for monitoring currents in alternating and rotating current networks. It is designed for detecting overcurrents in the measurement range of 5 to 50 A and is intended for installation in enclosures. The device operates on the zero-current principle, whereby the output relay is not activated in the event of a fault, ensuring safe disconnection in case of overload. The auxiliary voltage is AC 220–240 V, and the width is 70 mm, making it suitable for standard enclosure mounting.
Applications
This relay is designed for use in industrial and commercial installations where reliable current monitoring is required. It is suitable, for example, for protective functions in drive technology, pump control systems, lighting installations, or for monitoring electrical machines. The galvanic isolation between the auxiliary circuit and the measurement circuit increases safety and prevents interference in the control circuit.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used for controlling auxiliary devices or signal indication. The pickup value is adjustable, allowing the relay to be adapted to different load profiles. The hysteresis is fixed at approximately 4 %, ensuring stable switching behavior during current fluctuations. The time delay is adjustable in the range of 0.1 to 20 seconds, to account for or ignore short-term current peaks.
Technology Explained Simply
The relay integrates a current transformer, which taps the measurement current from the main circuit and converts it into a measurable signal. Measurement is performed in the range of 5 to 50 A, with precise adjustment achieved via jumpers on terminals 11, 12, and 14. The LED indicators signal the operating status: a green LED indicates that the current is within the permissible range, while a red LED lights up when the switching point is exceeded. The indication is independent of the auxiliary voltage, as the LED indicators are directly connected to the measurement circuit.
Compatibility and Accessories
The device is part of the SP series from Dold and can be installed in enclosures with mounting plate and cable duct. It is compatible with other devices in the series, such as the SP 9270, and can be mounted together in systems with similar widths (70 mm). The S form factor with a depth of 100 mm and top-mounted connection terminals is intended for enclosure applications.
Mounting and Installation
Mounting is carried out in enclosures using a mounting plate. The connection terminals are arranged on top, enabling easy wiring. The width of 70 mm corresponds to the standard for enclosure devices, allowing the device to be easily integrated into common enclosure modules. The auxiliary voltage is connected via terminals A1 and A2, while the measurement circuits are connected via terminals i1, k1, i2, k2, i3, k3.
Operational Advantages
The adjustable time delay allows flexible adaptation to the specific application, thereby avoiding unwanted disconnections due to short-term load peaks. The galvanic isolation between the auxiliary and measurement circuits increases safety and prevents interference. The LED indicators provide visual feedback on the operating status, simplifying maintenance and diagnostics. The device complies with the standard IEC/EN 60255-1, ensuring reliability and safety in industrial applications.