Further information for Dold 0064814 RP9810.13 3/N AC400/230V >30KVA voltage/frequency monitor
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Distribution board
Output contacts
3 C/O contacts
Width
70 mm
Type
RP 9810
Operate delay
Variant
Contact equipping
3 changeover contacts
Generator system power
> 30 kVA
Supply voltage
3/N AC 400/230 V
The voltage and frequency monitor RP9810.13 from Dold is an industrial monitoring device for self-generation systems in low-voltage networks, specifically designed for systems with a power output exceeding 30 kVA. The device monitors the network voltage and frequency of the grid operator and ensures safe and standard-compliant disconnection of the generation system in case of faults. It features a dual-channel design, with each channel operating via its own output relay, enabling a single-fault-safe function. The voltage and frequency threshold settings are adjusted using detent rotary switches, which are pre-set according to VDE-AR-N 4105:2011-08 at time of delivery. The front cover is sealable to prevent tampering.
Applications
This device is intended for use in various types of self-generation systems, including photovoltaic systems, wind power plants, combined heat and power plants, and hydropower plants. It serves for grid and system protection, particularly for non-regulated generation systems, and is suitable for use in accordance with EEG 2012 and SysStabV. Monitoring is performed in three phases, measuring voltages between line conductors and neutral conductor. Additionally, line-to-line voltages are calculated and evaluated. Frequency measurement is performed single-phase in phase L1.
Functions and Equipment in Detail
Disconnection of the generation system occurs when the network voltage or frequency exceeds or falls below the set threshold values. Reconnection is only possible if voltage and frequency remain continuously within the tolerance range for the adjustable time delay tW. In case of a short interruption, reconnection is triggered after 5 seconds, provided the values are stable. The threshold for undervoltage protection is fixed at 80 % of nominal voltage. An additional fault indicator relay signals malfunctions. Display is provided via a multi-coloured, illuminated LCD screen, showing operating status, measured values, and fault memory. The display can be switched using a button.
Technology Explained Simply
The RP9810.13 is designed as an installation distributor in form 4TE, with a width of 70 mm. The device function is based on a redundant, dual-channel structure, ensuring high reliability. The output contacts consist of three changeover contacts, each controlling a coupling switch. A release input allows integration with round control receivers. Island grid detection identifies whether the network is disconnected from the public power grid, ensuring safe reconnection control.
Compatibility and Accessories
The device is designed for use in systems with a power output exceeding 30 kVA, with an option available for systems ≤ 30 kVA. It complies with standards VDE-AR-N 4105:2011-08, DIN VDE 0126-1-1:2013-08, and DIN EN 60255-1. The connection terminals are designed for connection to network lines (L1, L2, L3/N) as well as for controlling the coupling switches (channels 1 and 2) and the fault indicator relay. The feedback circuits of the coupling switches (KA, KE) enable status feedback of the switch position to the device.
Mounting and Installation
The device is mounted in an installation distributor and is designed for mounting height 4TE (70 mm width). The connection terminals are clearly labelled, enabling easy and secure wiring. Settings are adjusted via rotary switches on the front panel, which can be sealed after commissioning. The LCD display enables quick diagnosis and status monitoring.
Advantages in Operation
The single-fault-safe, dual-channel structure increases reliability. Simple adjustment via rotary switches and simultaneous visibility of all values simplify commissioning. Randomized disconnection in the range of 50.2 Hz to 51.5 Hz prevents unwanted reconnections. High measurement accuracy and fault memory support maintenance and fault analysis. The device is suitable for use in industrial and commercial systems connected to the public low-voltage network.