Dold 0064784, EAN: 4030641647841

Dold 0064784 undervoltage relay AC24V 0,7-1,0UN4%

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0064784 undervoltage relay AC24V 0,7-1,0UN4%

Lieske Part No. 1330836
Mfg Part No 0064784
EAN-Code 4030641647841
Manufacturer Dold
Here only 121,00 EUR
143,99 EUR incl. VAT

Further information for Dold 0064784 undervoltage relay AC24V 0,7-1,0UN4%

Technical data
1- / 3-phase1
Auxiliary voltageWithout
Enclosure designDistribution board
Nominal voltage max.AC 230 V, DC 125 V
Output contacts1 C/O contact
Width17,5 mm
TypeIK 9173
Operate delayYes
Variant
Contact equipping1 changeover contact
Nominal voltageAC 24 V
Response value0,7 - 1,0 Un 4%
Time delay0,5 - 20 s
VariantNC circuit operation. Settable time delay t1. Settable response value
The Dold undervoltage relay IK9173.11/030 AC24V 0,7-1,0UN4% is a single-phase monitoring device for detecting undervoltages in alternating current networks. It is used for continuous network monitoring and enables automatic switching to safety power supply or safety lighting in accordance with DIN VDE 0100-710 or DIN VDE 0108. The device operates on the principle of residual current, whereby the output relay is not activated in the event of a fault, ensuring safe and reliable operation. Measurement is carried out via the arithmetic mean of the voltage between line and neutral conductor (L-N), thus achieving precise and reliable monitoring.

Applications
This relay is suitable for use in industrial and railway applications, particularly in environments with unstable power grids, such as local power generation or grids in the 2nd and 3rd world. It is used to immediately switch off specific load groups in overloaded networks and to reconnect them only after a defined waiting period. This is especially useful when, after a brief power failure, certain loads such as compressors or machining machines must not be switched on immediately. The reconnection delay t2 for returning to normal condition can be set between 0.1 and 20 minutes, enabling a staged restart of loads.

Functions and Equipment in Detail
The device features an adjustable pickup value in the range of 0.7 to 1.0 times nominal voltage (Un) with a hysteresis of approximately 4 %. The delay time t1 for fault indication is adjustable between 0.5 and 20 seconds and is only effective as long as the phase voltage L-N is at least 0.5 times nominal voltage. The response time of the input circuit in the event of phase failure is approximately 100 ms. The output contacts consist of a changeover contact (11-12-14) with a contact material of silver-nickel (AgNi). The rated operating voltage is AC 250 V, and the thermal current Ith is 4 A. The switching capacity according to AC 15 is 3 A/AC 230 V for the make contact and 1 A/AC 230 V for the break contact.

Technology Explained Simply
The relay monitors the supply voltage and reacts when it falls below the set pickup value. Upon reaching the pickup value, the output changeover contact is actuated, enabling an external circuit such as an alarm or shutdown to be triggered. The LED indicator lights yellow when the output relay is activated (contact 11-14 closed). The delay time t1 ensures that the fault indication is only issued after a certain delay, ignoring short-term voltage fluctuations. The delay time t2 enables controlled restart after a power failure.

Compatibility and Accessories
The device is designed for a nominal voltage of AC 24 V, with a maximum nominal voltage up to AC 230 V and DC 125 V. It is designed for use in installation and industrial distributors according to DIN 43880. The width is 17.5 mm, and the depth is 59 mm. The connection terminals are located at the bottom. The devices are certified according to IEC/EN 60255-1, ensuring compliance with standards for electrical equipment for measuring and protective devices.

Mounting and Installation
The relay is intended for mounting in installation and industrial distributors according to DIN 43880. The connection terminals are located at the bottom, enabling easy and secure wiring. The devices are designed for continuous operation and can be operated in a temperature range from -20 °C to +60 °C. The relative humidity must not exceed 93 % at 40 °C, and the operating altitude is limited to a maximum of 2000 m.

Operational Advantages
Early detection of impending failures enables preventive maintenance measures and prevents costly damage. The high availability and operational reliability of the system are ensured by reliable network monitoring. The adjustable pickup values and time delays allow flexible adaptation to different requirements and network conditions.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1330836
qrcode für Dold 0064784 undervoltage relay AC24V 0,7-1,0UN4%