Further information for Dold 0064527 SL9079.12/103 3AC500V 0.7-1.05UN voltage relay 0.2-2s
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3 AC 500 V
Output contacts
2 C/O contacts
Width
35 mm
Type
SL 9079
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 500 V
Response value
0,7 - 1,05 Un
Time delay
0,2 - 2 s
Variant
For 3p3w systems. Adjustable response value. With transformator for mains with harmonic content
The voltage relay SL9079.12/103 from Dold is a monitoring device for three-phase power networks, specifically developed for detecting short-term voltage interruptions. It ensures stable operation in control systems, particularly in contactor and PLC systems, where brief power interruptions can lead to uncontrolled states. The device detects voltage drops or phase failures, for example caused by lightning strikes or switching operations in the network, and responds with an adjustable re-energizing delay to generate a defined reset pulse. This prevents individual components of a control system from restarting asynchronously, which could lead to malfunctions.
Applications
This relay is designed for use in industrial and technical installations where reliable network monitoring is required. It is mounted in enclosures and is suitable for applications in manufacturing automation, power supply technology, and installations with sensitive control technology. The ability to be connected single-phase expands its application range, for example in systems that only provide one phase. Monitoring is independent of phase sequence, which simplifies installation.
Functions and Equipment in Detail
The device monitors voltage in a 3-phase network with a rated voltage of 3 AC 500 V. It detects voltage interruptions as short as 20 ms, which is sufficient for most transient disturbances. The pickup value is adjustable within the range of 0.7 to 1.05 times rated voltage, allowing sensitivity to be adapted to the specific requirements of the installation. The drop-out value is also adjustable and ranges between 0.55 and 1.05 Un, with a hysteresis of 4 %. This ensures stable switching behavior without oscillations during fluctuating voltages.
Technology Explained Simply
The relay operates on the standby current principle, where the output relay is not activated in the event of a fault, but only after voltage recovery above the pickup value and after the adjustable delay time has elapsed. The re-energizing delay is adjustable between 0.2 and 2 seconds and serves to generate an extended reset pulse. This pulse ensures that all control components return synchronously to a defined initial state. The green LED indicates the normal condition, meaning the output relay is activated and voltage is within the specified range.
Compatibility and Accessories
The device is designed for networks without a neutral conductor and features an integrated transformer power supply, making it suitable for networks with harmonic distortion. It is available in the SL 9079 form factor, which has a width of 35 mm and a depth of 98 mm, with top-mounted connection terminals for installation in enclosures with mounting plate and cable duct. The terminals are designed for connection to L1, L2, L3 and N; for single-phase connection, terminals L1, L2 and L3 must be bridged. The output contacts consist of 2 changeover contacts, rated for a load up to 4 A thermally.
Mounting and Installation
Mounting is done in enclosures using a mounting plate. The connection terminals are arranged on top, which facilitates cabling in the cable duct. The devices are certified according to IEC/EN 60255-1, confirming compliance with safety and functional standards for electrical equipment in measurement and monitoring technology. The rated frequency is 50/60 Hz, and the rated consumption is approximately 8 VA.
Advantages in Operation
Thanks to the adjustable delay time and precise voltage monitoring, the reliability of control systems is increased. The device prevents unintended restarts and enables an orderly return to operational status after a disturbance. The green LED indicator provides visual feedback on the operating status, simplifying maintenance and diagnostics. Configuration as a fault memory (re-energizing lockout) is also possible to prevent certain installations from automatically restarting after a fault.