Dold 0064241, EAN: 4030641642419

Dold 0064241 emergency stop module LG5925.02/61 AC/DC24V

Industrial Material > Industrial relays and contactors > Industrial Timers

Dold 0064241 emergency stop module LG5925.02/61 AC/DC24V

Lieske Part No. 447115
Mfg Part No 0064241
EAN-Code 4030641642419
Manufacturer Dold
Here only 210,32 EUR
250,28 EUR incl. VAT

Further information for Dold 0064241 emergency stop module LG5925.02/61 AC/DC24V

Technical data
1- / 2-channel1, 2
ApprovalsUL
Cat. / PL acc. to EN ISO 13849-14/e
ConnectionPluggable cage clamp terminals, Pluggable screw terminals, Screw terminals
Output contacts max.4 NO contacts
SIL acc. to IEC/EN 620613
Thermal current Ith max.8 A
Width22,5 mm
TypeLG 5925
Cross fault detectionYes
Suited as safety gate monitorYes
Variant
Contact equipping2 NO contacts
Nominal voltageAC/DC 24 V
Terminal typescrew terminals fixed
Approvals and MarkingsUL-listed C/US, TÜV, UKCA, CCC
The Dold emergency stop module LG5925.02/61 AC/DC24V is a safety-relevant switching component for use in industrial plants, particularly for safeguarding machines and protective doors. It is used for hazard disconnection and is employed in emergency stop circuits, monitoring of sliding protective grilles, and in combustion systems operating continuously in accordance with EN 50156-1. The device is designed for the disconnection of the entire fuel supply in combustion systems as specified in EN 50156-1 section 10.5.5.2. It has a width of 22.5 mm and is designed for mounting in standard control panels. The nominal voltage is AC/DC 24 V, making it suitable for use in many industrial control systems.

Applications
This module is specifically designed for safety-critical applications where reliable disconnection in an emergency is required. It is used in machine construction, manufacturing plants, and in energy supply, particularly in systems certified according to EN 50156-2 for combustion systems. As a protective door monitor, it is suitable for monitoring access to hazardous areas and triggering disconnection when the protective door is opened. Its use in continuous operation systems requires high reliability, which is ensured by the safety certifications.

Functions and Equipment in Detail
The device features 2 normally open (NO) contacts as standard contact configuration, with up to 4 NO contacts per device being realizable. The connection technology includes fixed screw terminals, with removable screw and spring-cage terminals also available as an option. Wire connections can be made with stranded wires up to 2 x 1.5 mm² with ferrules and plastic sleeves, or with solid conductors up to 2 x 2.5 mm² according to DIN 46228-1/-2/-3/-4. The LED indicators show the operating voltage status and the status of channels 1 and 2, enabling quick diagnosis of faults. Activation is achieved via a single-button switch or via an automatic start function, which can be set using switch S2.

Technology Explained Simply
The module is designed for single- or dual-channel wiring, allowing flexible integration into different safety concepts. Short-circuit detection at the single-button switch enables detection of short circuits in the control circuit, increasing safety. The thermal current rating is up to 8 A, defining the contact load capacity. The safety functions are certified according to international standards: it complies with Performance Level (PL) e and Category 4 according to EN ISO 13849-1, as well as Safety Integrity Level (SIL CL) 3 according to IEC/EN 62061. Additionally, it meets SIL 3 requirements according to IEC/EN 61508 and IEC/EN 61511, confirming its suitability for high-safety applications. Certifications include UL-listed C/US, TÜV, UKCA, and CCC, ensuring international usability.

Compatibility and Accessories
The device is compatible with various connection technologies, including removable spring-cage and screw terminals, facilitating replacement and maintenance. Optional plug-in terminal blocks are available, enabling quick device replacement. Its use in combination with other safety components, such as emergency stop switches or protective door switches, is intended. The certifications and safety standards ensure compatibility with other safety-relevant components within an overall system.

Mounting and Installation
Mounting is carried out in standard control panels with a width of 22.5 mm. The connection terminals are designed for use with stranded and solid conductors, with exact cross-sections specified in the datasheet. The LED indicators facilitate commissioning and fault diagnosis. Switches S1 and S2 allow configuration of short-circuit detection and the automatic start function, enabling adaptation to specific applications. Installation is carried out according to the technical instructions in the datasheet, with correct wiring and compliance with safety regulations being essential.

Operational Advantages
The high safety certification (PL e, Cat. 4, SIL 3) ensures reliable operation in critical applications. The LED indicators enable quick status monitoring, and short-circuit detection increases fault tolerance. The flexible connection technology and the option for single- or dual-channel wiring enhance adaptability to different systems. Certifications according to UL, TÜV, UKCA, and CCC facilitate use in various markets. The module is designed for continuous operation, ensuring suitability for continuously running plants.