| Technical data |
| 1- / 2-channel | 1, 2 |
| Approvals | UL |
| Cat. / PL acc. to EN ISO 13849-1 | 4/e |
| Connection | Pluggable cage clamp terminals, Pluggable screw terminals, Screw terminals |
| Output contacts max. | 1 NC contact, 5 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 5 A |
| Width | 22,5 mm |
| Type | LG 5929 |
| Variant |
| Contact equipping | 5 NO contacts, 1 NC contact for feedback circuit |
| Nominal voltage | AC 230 - 240 V |
| Terminal type | fixed terminal blocks with screw terminals |
| Approvals and Markings | UL-listed C/US, TÜV, CCC |
| Variant | For 1-channel connections |
The Dold expansion module LG5929.60/61 AC230-240V is a safety relay for use in industrial control systems, particularly for safe contact multiplication and amplification in safety applications. It is used in conjunction with suitable switching devices or controls to provide additional safety circuits when a primary safety module is insufficient. The device is designed for single-channel wiring, but can also be used in dual-channel applications. It features forced-guided contacts, ensuring a safe and reliable switching function, and is equipped with an operational status indicator to allow visual verification of the operating state.
Applications
This module is designed for use in safety-critical installations, particularly in applications that must comply with EN ISO 13849-1 and IEC/EN 62061 requirements. It can be used in combustion systems according to EN 50156-1. Control is via safety-oriented semiconductor outputs, such as BWS switches or emergency stop switches. The maximum safety performance level is Category 4 and Performance Level e according to EN ISO 13849-1, as well as SIL 3 according to IEC/EN 62061. The certifications UL-listed C/US, TÜV, and CCC confirm suitability for use in various markets.
Functions and Equipment in Detail
The device provides contact configuration with five normally open contacts (NO) and one normally closed contact (NC) for feedback circuit. This configuration enables safe signal transmission and feedback of the operating status. The contacts are forced-guided, meaning they are mechanically linked, thus eliminating the risk of malfunction due to mechanical wear or failure of a single contact. The maximum thermal current rating is 5 A, enabling use in systems with moderate loads.
Technology Explained Simply
The connection technology includes fixed terminal blocks with screw terminals, ensuring a secure and durable connection. Optional removable spring-cage terminals and removable screw terminals are available, enabling quick replacement of the device. Wire connections can be made with stranded conductors up to 2 x 1.5 mm² with ferrules and plastic sleeves, or with solid conductors up to 2 x 2.5 mm². The width is 22.5 mm, allowing compact mounting in standard control panels. The nominal voltage is AC 230–240 V, enabling use in standard mains voltage systems.
Compatibility and Accessories
The expansion module is suitable for use in single- and dual-channel wiring and can be combined with other safety modules to increase the number of available safety contacts. It is designed for use with safety-oriented semiconductor outputs, facilitating integration into modern control systems. The certifications UL, TÜV, and CCC ensure compatibility with international safety standards.
Mounting and Installation
Mounting is in standard control panels with a width of 22.5 mm. The terminal blocks are fixed, with optional removable variants available with spring-cage or screw terminals. The connection terminals are designed for stranded and solid conductors, with maximum cross-sections of 1.5 mm² (stranded) and 2.5 mm² (solid). Mounting requires no additional tools, as the terminal blocks are inserted directly into the control panel.
Operational Advantages
The module provides safe and reliable contact multiplication, increasing the number of available safety contacts without compromising safety integrity. The forced-guided contacts ensure high reliability, and the operational status indicator allows for quick visual inspection of the operating state. The combination of compact design and high safety performance makes the device a suitable solution for industrial applications where safety and reliability are paramount. The certifications UL, TÜV, and CCC, along with compliance with EN ISO 13849-1 and IEC/EN 62061, confirm suitability for use in safety-critical installations.
Safety Standards and Certifications
The device meets the requirements of EN ISO 13849-1 with Category 4 and Performance Level e, as well as IEC/EN 62061 with SIL 3. The certifications UL-listed C/US, TÜV, and CCC confirm compliance with international safety standards. Use in combustion systems according to EN 50156-1 is also permitted. The maximum safety performance is supported by forced-guided contacts and the operational status indicator, ensuring safe and reliable operation.