Further information for Dold 0064033 semiconductor contactor AC230-480V AC50A
Technical data
Analog Input Control
4 - 20 mA
Approvals
UL
Load current up to
50 A
Load voltage up to
AC 480 V
Number of poles
1-pole
Width
22,5 mm, 45 mm, 90 mm
Type
BF 9250/0_2
Temperature monitoring
Variant
Auxiliary voltage
AC/DC 24 V
Contact equipping
without signal contact
Control input
DC 4 - 20 mA
Load current
AC 50 A
Load voltage
AC 230 - 480 V
Semiconductor output
1-pole
Approvals and Markings
UL-listed C/US
Variant
Self optimising, to achieve as short as possible control periods, suitable for infrared lamps
The Dold semiconductor contactor BF9250.91/042 UH=AC/DC24V DC4-20mA is an industrial power semiconductor for pulse packet control of heating elements. It is used for precise temperature control in systems where fast, noiseless, and reliable switching function is required. The device features a single-pole semiconductor output and is designed for load voltages up to AC 480 V and load currents up to AC 50 A. Control is achieved via an analog input in the range DC 4–20 mA, enabling precise actuation of the heating load. The auxiliary voltage is AC/DC 24 V, allowing flexible integration into existing control systems.
Applications
This contactor is specifically designed for controlling resistive loads such as heating rods, infrared lamps, or other resistance heaters. The self-optimized pulse distribution with minimized cycle times makes it particularly suitable for infrared lamps, where short switching cycles and high switching speed are required. The zero-voltage switching function reduces electrical interference and extends the lifespan of the load. The width of the device is 90 mm, corresponding to the maximum rated current class of 50 A.
Functions and equipment in detail
The device features an LED indicator that visually signals the operating status: green for supply voltage, yellow for activated output, and red for faults. In case of synchronization errors, control input errors, or overheating of the power semiconductor, the red LED blinks. The overheating alarm is latching and requires a brief interruption of the supply voltage to reset. The temperature protection function protects the power semiconductor from overheating. A varistor protection safeguards the device against voltage surges.
Technology explained simply
Pulse packet control (Burst-Firing) switches the load in short, controlled pulses, enabling precise temperature regulation. The zero-voltage switching function ensures that the switch operates only at the zero crossing of the mains voltage, minimizing network interference. Control is performed via an analog input, which can operate either as a current signal (DC 4–20 mA) or as a voltage signal (DC 0–10 V). The resolution of the output control is 5 %, allowing fine adjustment of the power. The maximum air humidity is 75 % without condensation, and the operating temperature range is between 0 °C and 40 °C.
Compatibility and accessories
The contactor is designed for loads in the voltage range AC 230–480 V and a rated current up to AC 50 A. It is intended for resistive loads and can be used in systems with frequencies between 45 Hz and 65 Hz. The devices are DIN rail mountable, enabling easy integration into enclosures. The certifications include UL-listed C/US, allowing use in the USA and Canada. The standards IEC/EN 60947-4-2 and IEC/EN 60947-4-3 are complied with, ensuring safety and reliability in industrial applications.
Mounting and installation
The device is snap-on mountable onto DIN rail, enabling quick and secure installation in enclosures. Recommended clearances to the surrounding environment are 20 mm above and below, and 10 mm to the right and left, to ensure sufficient cooling. The connection terminals are clearly labeled: A1 (+) and A2 for auxiliary voltage, X1 for control input, L1/N for mains connections, and T1/N for load output. Installation must comply with electrical safety regulations.
Advantages in operation
The semiconductor contactor provides a noiseless and fast switching function, extending the lifespan of heating elements. Precise temperature control via the analog input enables high process accuracy. The integrated fault indication with LED signals facilitates diagnosis during operation. The zero-voltage switching function reduces network interference, and the varistor protection enhances operational safety. The self-optimized pulse distribution ensures particularly efficient control for infrared lamps.