| Technical data |
| 1- / 3-phase | 1 |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | AC 500 V, DC 450 V |
| Output contacts | 2 C/O contacts |
| Width | 22,5 mm |
| Type | MK 9054N |
| Variant |
| Auxiliary voltage | AC/DC 80 - 230 V |
| Contact equipping | 2 changeover contacts |
| Measuring range | AC 25 - 250 V |
| Operate delay | 0,1 - 20 s |
| Switching delay | 0 - 20 s |
| Terminal type | fixed terminal block with screw terminal |
| Approvals and Markings | CCC |
| Variant | Overvoltage relay. Energized on trip |
The voltage relay MK9054N.12/010 from Dold is an
overvoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC voltage networks. It serves preventive system monitoring to avoid failures by early detection of voltage fluctuations and to increase the operational safety of electrical systems. The device operates on the
operating current principle and is designed for use in enclosures, with a width of 22.5 mm enabling compact mounting in standard control panels.
Applications
This relay is intended for industrial applications, particularly in systems requiring continuous voltage monitoring, such as in manufacturing technology, power supply, or automation technology. It monitors voltages in the range AC 25–250 V and is suitable for measurement frequencies up to 5 kHz. The galvanic isolation between auxiliary circuit and measurement circuit ensures safe and interference-free measurement, even at high network voltages. Device settings are adjusted via rotary switches on the front, enabling simple and user-friendly calibration.
Functions and Equipment in Detail
The device features
2 changeover contacts as output contacts, which can be used to control auxiliary circuits or alarm systems. The pickup delay ranges from 0.1 to 20 seconds, and the dropout delay from 0 to 20 seconds, enabling precise response to voltage fluctuations. The start-up bypass activates once upon applying auxiliary voltage to prevent unwanted switching operations during startup. The auxiliary voltage is in the range AC/DC 80–230 V, allowing flexible integration into various power supply systems.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value, ensuring accurate measurement even with sinusoidal voltages. The pickup value and hysteresis are adjusted via rotary switches on the device front. The hysteresis depends on the set pickup value, ensuring stable switching behavior during minor voltage fluctuations. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED), enabling quick fault localization.
Compatibility and Accessories
The device is designed for industrial environments and complies with standards IEC/EN 60255-1 and IEC/EN 60947-1. It can optionally be equipped with a remote potentiometer to adjust the pickup value externally. The terminal type is a fixed terminal block with screw terminals, ensuring a secure and durable connection. The maximum rated voltage is AC 500 V and DC 450 V, with measurement ranges up to 500 V.
Mounting and Installation
Mounting is done in enclosures, with the width of 22.5 mm allowing standard installation in 35-mm grids. Connections are made via screw terminals, ensuring a secure connection. When using a remote potentiometer, ensure that the measurement circuit and remote potentiometer are not galvanically isolated. Therefore, terminal “e” should be connected to “N”, “-”, or GND to avoid dangerous phase voltage at the remote potentiometer.
Operational Advantages
Thanks to precise and reliable voltage monitoring, the relay provides protection against device damage due to overvoltage. The possibility of preventive maintenance and quick fault localization via LED indicators increases productivity and reduces downtime. High overload capacity and galvanic isolation between measurement and auxiliary circuits ensure robust and safe operation even in demanding environments.