| Technical data |
| Load current up to | 125 A |
| Load voltage up to | AC 600 V |
| Number of poles | 1-pole |
| On/Off Input Control | AC/DC, DC |
| Width | 45 mm |
| Type | PH 9260 |
| Variant |
| Control voltage | DC 4 - 32 V |
| Load current | AC 50 A |
| Load voltage | AC 200 - 480 V |
| Semiconductor output | 1-pole |
| Variant | Switching at voltage maximum. Without heat sink |
The Dold semiconductor relay PH9260.91/020 AC200-480V AC50A is an
AC semiconductor relay for use in industrial applications. It is designed for wear-free and noiseless switching of loads in the alternating current range, particularly for frequent switching operations. The device is designed as
peak-voltage switching, making it especially suitable for operating transformers, as it avoids the high inrush current. Control is achieved via a
DC control voltage in the range of 4 to 32 V, allowing flexible integration into existing control systems.
Applications
This relay is intended for use in various industrial applications, including control of heaters, motors, valves, and lighting systems. It is particularly suitable for machines in the plastics and rubber industry, packaging machines, soldering systems, and in the food industry. The peak-voltage switching variant is specifically suited for transformers, as it minimizes the high inrush current and thus increases the service life of the load.
Functions and Features in Detail
The device features a
single-pole semiconductor output and is designed for a load voltage of AC 200 to 480 V. The rated load current is AC 50 A, with the device designed for load currents up to 125 A (AC-51). Switching occurs at the next voltage zero crossing when the control voltage is applied, ensuring disturbance-free switching with minimal electromagnetic radiation. An
LED status indicator signals the state of the control input. The terminals are designed as
box terminals, enabling secure and easy connections.
Technology Explained Simply
The relay is based on two
antiparallel-connected thyristors, which handle current conduction in the AC circuit. The
DCB technology (Direct-Copper-Bonding) ensures excellent heat transfer, reducing thermal stress on the component. The
peak blocking voltage is 1200 V or 1600 V, and the
insulation voltage is 4000 V, ensuring high electrical safety. The device complies with
IEC/EN 60947-4-3 standards and thus offers standardized quality for industrial applications.
Compatibility and Accessories
The relay is designed for operation in industrial environments and meets the requirements for
shock protection IP20. It is supplied without a heatsink, although an optional heatsink is available for mounting on a DIN rail. For thermal protection, a temperature limit switch (e.g., UCHIYA type UP62–100) can be installed in the designated pocket on the device. The
mounting width is 45 mm, enabling compact installation on standard DIN rails.
Mounting and Installation
Mounting is done on a DIN rail, with the box terminals providing secure connections to the wiring. Terminal designations are clearly defined: A1/A2 for the control input, L1 for the mains connection, and T1 for the load output. Installation requires no special tools, and the terminal connections are designed for quick and secure attachment.
Operational Advantages
The relay offers wear-free operation, as it has no mechanical contacts. Switching operations are noiseless and allow for high switching frequencies. The peak-voltage switching function reduces the inrush current surge for inductive loads, increasing the service life of the load. The LED indicator facilitates diagnosis and maintenance, as the operating status can be visually monitored. The high insulation strength and robust construction ensure reliable performance in demanding industrial environments.