Further information for Dold 0062256 asymmetrical relay AC/DC24V AC4-50A
Technical data
1- / 3-phase
3
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
70 mm
Type
SP 9278CT
Operate delay
Variant
Auxiliary voltage
AC/DC 24 V
Contact equipping
2 changeover contacts
Measuring range
4 - 50 A
Time delay
0,1 - 20 s
Variant
3-phasiges Strom-Asymmetriereleis mit Durchführungsstromwandler. Asymmetrieeinstellung 5 - 35 %
The Dold current asymmetry relay SP9278.12CT/001 AC/DC24V AC4-50A is a 3-phase monitoring device for controlling current symmetry in three-phase networks. It is designed for continuous monitoring of three current paths, for example in heating circuits, load circuits or industrial plants, to detect uneven load distribution at an early stage. The device features integrated current transformers that can measure currents in the range of 4 to 50 A, with the measurable range varying depending on the set asymmetry. The asymmetry is continuously adjustable in the range of 5 to 35 %, with the device using the two current paths with the smallest percentage difference as reference value to calculate the deviation of the third path.
Applications
This relay is designed for use in industrial enclosures and is particularly suitable for applications where stable current distribution across all three phases is required. Typical applications include monitoring of heating elements, electric heating systems, motors or load circuits, where asymmetry can lead to overheating, inefficient operation or damage. The galvanic isolation between auxiliary circuit and measurement circuit ensures safe and interference-free signal transmission.
Functions and equipment in detail
When asymmetry occurs, after an adjustable delay time of 0.1 to 20 seconds, a fault is reported via two changeover contacts. The output contacts can be operated in either the active current principle (output relay activated in case of fault) or the passive current principle (output relay deactivated in case of fault). The red LED displays a flashing code that identifies the faulty phase. Without a bridge across X1-X2, the fault is stored; with a bridge, an automatic reset process is initiated. The /1xx variant also offers the remote reset function, where applying control voltage to X1(+) - X2 clears the fault storage or switches the device to non-storage operation.
Technology explained simply
The integrated current transformers in the lower part of the housing enable current measurement without additional terminals – the conductors are simply passed through the transformers. The response time is approximately 500 ms, and the temperature dependence of the measurement result is ≤ 0.05 % per Kelvin. The frequency of the measured current is in the range of 50 to 400 Hz. The auxiliary voltage is AC/DC 24 V, enabling flexible integration into existing control systems. The width of 70 mm corresponds to the standard for enclosure devices and ensures compact mounting.
Compatibility and accessories
The device is specified according to IEC/EN 60255-1 and designed for use in industrial environments. It is intended for operation in enclosures and can be combined with other components of the Dold product range, particularly in systems for monitoring electrical parameters. The integrated current transformers allow direct passage of the conductors, eliminating the need for additional connection terminals.
Mounting and installation
Mounting is carried out in an enclosure, with the width of 70 mm determining the mounting height. The current conductors are passed through the integrated current transformers in the lower part of the housing. The auxiliary voltage is connected to the appropriate terminal clamps. The asymmetry and time delay settings are adjusted using the designated adjustment options on the device. The LED indicators support diagnosis and fault localization.
Advantages in operation
Continuous monitoring of current symmetry enables preventive maintenance and contributes to higher productivity, as faults can be detected and rectified early. The quick fault localization via the flashing code of the red LED reduces downtime. The galvanic isolation between measurement and auxiliary circuit increases system safety and stability. The integrated current transformers and compact design simplify installation and maintenance in the enclosure.