Dold 0062046, EAN: 4030641620462

Dold 0062046 load monitor 3AC24-400V

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0062046 load monitor 3AC24-400V

Lieske Part No. 1338900
Mfg Part No 0062046
EAN-Code 4030641620462
Manufacturer Dold
Here only 395,86 EUR
471,07 EUR incl. VAT

Further information for Dold 0062046 load monitor 3AC24-400V

Technical data
1- / 3-phase3
Enclosure designSwitch cabinet
Measuring range max.12 A (8 kW)
Output contacts2 x 1 C/O contacts
Width45 mm
TypeMH 9397
Variant
Auxiliary voltageAC 230 V
Contact equipping2 x 1 changeover contact
Measuring currentAC 12 A
Measuring voltage3AC 24 - 400 V
Operate delay0 - 10 s
VariantDe-Energized on trip
The load monitor MH9397.12/010 from Dold is an industrial active power meter for monitoring the load of 3-phase electrical consumers, particularly motors. The device operates on the idle current principle and monitors active power consumption in the range of 3AC 24 to 400 V and a measuring current of AC 12 A, corresponding to a maximum active power of 8 kW. It is designed for use in enclosures and has a width of 45 mm. The operating principle is based on measuring the current in one phase, assuming a symmetrical load distribution across all three phases, as is typical for motor loads.

Applications
This load monitor is suitable for functional monitoring of electrical industrial drives with variable loads. It detects early signs of wear or faults in machines and tools, enabling preventive maintenance and avoiding plant failures. The devices can also be used to monitor underload conditions, ensuring comprehensive load control. Applications are in industrial environments where reliable and precise load monitoring is required.

Functions and equipment in detail
The device features two independent output relays, each with a 1-changeover contact, used for overload and pre-warning functions. The trigger values for the relays can be adjusted via two rotary switches: one for fine adjustment and the other for selecting the range in eight steps from 0 to 8 kW. The response delay tv can be set between 0 and 10 seconds to suppress short-term load fluctuations and avoid unnecessary tripping. Status indication is provided by LEDs: a green LED indicates the presence of auxiliary voltage, while another LED signals the switching state of relay 1 (P1), with flashing indicating time delay and constant illumination indicating relay activation. A second LED (P2) indicates the state of the second relay, also with flashing and constant light functions.

Technology explained simply
Active power measurement is performed by measuring the current in phase L1, assuming symmetrical load distribution across all three phases. The auxiliary voltage is AC 230 V and is supplied via terminals A1/A2. Current supply is via terminals i and k, intended for feeding the motor current in phase L1. For currents exceeding the measuring range, an external current transformer is required. The relay outputs enable control of external switching devices or alarms. The devices comply with standard EN 60255-1, which defines requirements for electrical measuring instruments and installations in industry.

Compatibility and accessories
The load monitor is designed for use in 3-phase networks but can also be used with single-phase supply, provided terminals L2 and L3 are bridged. The connection terminals are either screw or spring-cage terminals, allowing flexible installation. Optional plug-in connection blocks are available to facilitate device replacement. The devices are designed for mounting in enclosures and can be integrated into existing control systems.

Mounting and installation
Mounting is done in an enclosure, taking into account the width of 45 mm. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, K/L1/i for current path, L1/L2/L3 for measuring voltage, and contacts 11/12/14 and 21/22/24 for relay outputs. Connection diagrams in the datasheet show the correct wiring. The response delay is adjusted via a dedicated rotary switch.

Advantages in operation
The devices enable precise and reliable load monitoring, accelerating fault localization and increasing productivity. Simple threshold setting and visual fault diagnosis via LEDs simplify commissioning and maintenance. The combination of overload and pre-warning functions enables proactive operational monitoring. The compact design and cost-effective implementation make the device an efficient solution for industrial applications. The devices are designed for industrial environments and offer robust and reliable operation.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1338900
qrcode für Dold 0062046 load monitor 3AC24-400V