The Dold emergency stop module LG5925.48/61 AC110-115V is a safety-relevant switching component for use in industrial plants, particularly for protecting machines and combustion systems. It is used for hazard disconnection and monitoring of sliding safety grilles, as well as for safeguarding door interlocks. The device is designed for operation with a nominal voltage of AC 110–115 V at 50/60 Hz and has a width of 22.5 mm, making it suitable for standard 35 mm control panels. The contact configuration includes 3 normally closed contacts and 1 normally open contact, with up to 4 normally closed contacts usable as output contacts. Connection is made via fixed screw terminals, with removable spring-loaded terminals and removable screw terminals also available as options.
Applications
This module is used in plants where safe disconnection in an emergency is required, for example in continuous operation combustion systems according to EN 50156-1. It meets the requirements for hazard disconnection of the entire fuel supply according to EN 50156-1, section 10.5.5.2. Additionally, it is suitable as a safety door monitor to supervise access to hazardous machine parts. The application is in safety-critical environments where high reliability and fault detection are required.
Functions and Equipment in Detail
The device supports 1- or 2-channel wiring, allowing flexible integration into different safety concepts. It features line break detection at the push-button, which detects incorrect operation or a short circuit in the control circuit. Activation occurs via the push-button or via an automatic start function, which can be set using switch S2. Cross-circuit detection in the emergency stop control circuit is optionally activatable via switch S1. LED indicators for channel 1, channel 2, and operating voltage enable visual monitoring of the operating status.
Technology Explained Simply
The safety functions of the module are based on standards EN ISO 13849-1 and IEC/EN 62061. It achieves a Performance Level (PL) e and Category 4 according to EN ISO 13849-1, indicating high safety performance in avoiding hazards during operation. Additionally, it meets the Safety Integrity Level (SIL CL) 3 requirement according to IEC/EN 62061, confirming its ability to detect and respond to faults in safety-critical systems. The thermal current Ith is up to 8 A, defining the contact load capacity. Certifications UL-listed C/US, TÜV, UKCA, and CCC confirm compliance with international safety standards.
Compatibility and Accessories
The module is designed for use in systems with 1- or 2-channel wiring. The terminal connections support stranded wires with 2 x 1.5 mm² with ferrule and plastic sleeve, as well as solid conductors with 2 x 2.5 mm² according to DIN 46228-1/-2/-3/-4. The use of spring-loaded terminals or screw terminals allows flexible installation on various connection types.
Mounting and Installation
Mounting is done in standard 35 mm control panels. The fixed screw terminal technology requires mechanical fastening of the wires, with maximum cross-sections according to DIN 46228 to be observed. The module should be positioned so that the LED indicators are clearly visible and accessibility for maintenance and diagnostics is ensured. Electrical connections are made according to the wiring diagrams described in the datasheet.
Advantages in Operation
The module provides high safety performance through integrated cross-circuit detection and line break detection, which detect incorrect operation and circuit faults. The LED indicators enable quick diagnosis of the operating status. The 1- or 2-channel wiring offers flexibility in system design. Certifications according to UL, TÜV, UKCA, and CCC ensure compliance with international safety requirements. The width of 22.5 mm allows compact installation in existing control panels.