Further information for Dold 0061152 BA9054/331 DC0,2-2V UH DC110-220V battery symmetry monitor
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
DC 220 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054/331
Operate delay
Variant
Contact equipping
2 changeover contacts
Measuring range
DC 0,2 - 2 V
Nominal voltage
DC 110 - 220 V
Start up delay
Without
Switching delay
10 s
Approvals and Markings
UKCA, CCC
Variant
Without separately auxiliary voltage
The Dold battery symmetry monitor BA9054/331 is an industrial monitoring switch for battery systems with a central tap, particularly for emergency power supplies. The device monitors the voltage symmetry of the two half-voltages of a battery and detects faults early, such as voltage inversion of individual cells, internal short circuits, or sulfation. If the half-voltages deviate by more than the set value over a period of 10 seconds, the output relay drops out, enabling an alarm message or shutdown of the system. This function supports preventive maintenance and increases the operational safety and availability of the installation.
Applications
The BA9054/331 is specifically designed for battery systems with voltages up to 300 V DC. It is used in industrial installations, emergency power supplies, and other critical power supply systems where high reliability of the battery system is required. Monitoring is performed via the central tap of the battery, connected to terminal M. The device is designed for use in enclosures and complies with the standard IEC/EN 60255-1.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits or alarms. The contacts are gold-plated, making them suitable for switching small loads – in the range of 1 mVA to 7 VA, 1 mW to 7 W, at voltages from 0.1 to 60 V and currents from 1 to 300 mA. The pickup delay is 10 seconds, filtering out short-term voltage fluctuations and avoiding false alarms. The reset delay is fixed at 98 % of the pickup value, ensuring a high repeatability of ≤ ± 0.5 %.
Technology Explained Simply
The BA9054/331 measures the arithmetic mean of the two half-voltages of the battery. The input sensitivity is in the measurement range DC 0.2 to 2 V. The maximum current draw in the central line is 12 μA, ensuring low battery load. The temperature dependence of the device is < 0.05 % per Kelvin, enabling stable operation over a wide temperature range. The operating voltage is derived directly from the battery voltage, with the device designed for voltages from DC 110 to 220 V.
Compatibility and Accessories
The device is part of the VARIMETER series and can be combined with other models such as the BA9054/332, designed for higher battery voltages up to 500 V and with a separate auxiliary voltage. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage (identical to battery voltage for BA9054/331), UB+ and UB- for battery connections, M for the central tap, and e as the adjustment reference point. The LED indicators show operational readiness (upper green LED) and activation of the output relay (lower green LED). A test button allows functional testing by pressing for at least 10 seconds.
Mounting and Installation
The device is intended for installation in enclosures and has a width of 45 mm. Mounting is done in the usual manner within an enclosure, with terminals connected according to wiring diagrams. The pickup value is set by measuring the battery half-voltages, with possible readjustment after operational time, as new batteries may initially be asymmetric.
Operational Advantages
The early detection of faults in the battery system enables preventive maintenance, preventing costly failures. The high repeatability and low temperature dependence ensure reliable operation. The gold-plated contacts and ability to switch small loads extend the application range. The integrated LED indicators and test button simplify commissioning and maintenance. The device is designed for industrial environments and complies with UKCA and CCC certifications.
Certifications and Markings
The device carries UKCA and CCC certifications, confirming compliance with applicable safety and quality requirements. The standard IEC/EN 60255-1 is adhered to, which applies to electrical measuring instruments and monitoring devices in industry.
Function of LED Indicators
Upper green LED: Illuminates when operating voltage is applied
Lower green LED: Illuminates when output relay is activated
Terminal Designations
A1, A2: Auxiliary voltage (identical to battery voltage for BA9054/331)
UB+, UB-: Battery voltage
M: Battery central tap
e: Adjustment reference point
11,12,14: 1st changeover contact
21,22,24: 2nd changeover contact
Use in Emergency Power Supplies
The BA9054/331 is particularly suitable for emergency power supplies, where high availability and reliability of the battery system are critical. Early fault detection enables targeted maintenance and prevents unexpected failures.
Certifications and Markings
The device carries UKCA and CCC certifications, confirming compliance with applicable safety and quality requirements. The standard IEC/EN 60255-1 is adhered to, which applies to electrical measuring instruments and monitoring devices in industry.
Use in Emergency Power Supplies
The BA9054/331 is particularly suitable for emergency power supplies, where high availability and reliability of the battery system are critical. Early fault detection enables targeted maintenance and prevents unexpected failures.