Technical data
Load current up to40 A
Load voltage up toAC 480 V
Number of poles1-pole
On/Off Input ControlDC
Width45 mm
TypePH 9270
Signalling outputYes
Variant
Auxiliary voltageDC 24 V
Load currentAC 40 A
Load voltageAC 200 - 480 V
Semiconductor output1-pole
VariantSwitching at zero crossing. Control via A1/A2 with under current monitoring and PNP transistor output with de-energized on trip. With heat sink
The Dold semiconductor contactor PH9270.91/001/02 AC200-480V AC40A is a 1-pole AC semiconductor relay for use in industrial applications where wear-free, noiseless, and frequent switching of loads is required. It is used for controlling and monitoring heating systems, motors, valves, and lighting systems. The device operates on the zero-voltage switching principle, activating at the next zero crossing of the sinusoidal mains voltage and deactivating at the next zero crossing of the load current. This minimizes electrical interference and extends the service life of load components. Control is via the digital input A1/A2 with an auxiliary voltage of DC 24 V.

Applications
This semiconductor contactor is designed for use in machine building and production plants, particularly in injection moulding machines, extruders, thermoforming and blow-moulding machines, packaging machines, soldering systems, and the food industry. It is suitable for applications requiring high switching frequency and reliable load monitoring. The integrated load circuit monitoring detects faults such as load circuit interruption, over- or under-current, missing load voltage, fuse failure, or thyristor defects. For overcurrent monitoring, the control system must account for a start-up bypass time.

Functions and Features in Detail
The device features a PNP semiconductor alarm output operating on the rest current principle, which activates when a fault is detected. Status indication is provided by a dual-color LED: the LED “A1/A2” indicates the status of the control input (yellow = activated, off = not activated), while the LED “Alarm” signals the device status (green = no fault, red = fault, off = no auxiliary voltage). The load voltage is AC 200 to 480 V, and the load current is AC 40 A. Monitoring is continuous when auxiliary voltage is applied (A3+/A2).

Technology Explained Simply
The device is based on two antiparallel-connected thyristors responsible for the power switching. The DCB technology (Direct-Copper-Bonding process) ensures optimal heat dissipation, reducing thermal stress and increasing service life. The width is 45 mm, enabling compact mounting on a DIN rail. Optionally, the device can be equipped with a heatsink, further improving heat dissipation and enabling DIN rail mounting. The protection class IP 20 safeguards against direct contact with moving parts.

Compatibility and Accessories
The semiconductor contactor is compliant with IEC/EN 60947-4-3 and suitable for use in PLC control systems. The alarm output is PNP-type; upon request, an NPN variant is also available. The integrated load circuit monitoring enables rapid fault detection. Optionally, a temperature limit switch (normally open) can be inserted into the designated pocket on the underside of the device to activate an over-temperature protection function. For thermal protection, for example, a temperature limit switch of type UCHIYA UP62–100 can be used.

Mounting and Installation
Mounting is on a DIN rail, with the device with heatsink snap-fitting onto the rail. Installation must be carried out by a qualified electrician. Terminal designations are as follows: A1+/A2 for the control input, A3+/A2 for the operating voltage and load circuit monitoring, Alarm for the semiconductor alarm output, L1 for the mains connection, and T1 for the load output. The connection terminals are clearly labeled to ensure safe and error-free installation.

Operational Advantages
The semiconductor contactor provides wear-free and noiseless switching, reducing maintenance and increasing operational safety. The integrated load monitoring enables early fault detection and prevents damage to the load or drive system. The zero-voltage switching minimizes electrical interference and extends the service life of load components. The combination of DCB technology and heatsink ensures efficient heat dissipation, increasing reliability under high loads. The PLC-compatible alarm output enables easy integration into existing control systems.