Further information for Dold 0060895 GB9034/0111 200A AC50/60Hz 400V motor brake unit
Technical data
Braking current adjustable up to max.
600 A
Braking time adjustable up to max.
320 s
Width
110 mm
Type
GB 9034
Automatic standstill monitoring
External brake contactor required
Signalling output
Temperature monitoring
Variant
Auxiliary voltage
Without
Braking current
200 A
Nominal voltage
AC 400 V
Approvals and Markings
UKCA
Variant
Brake current monitoring, thermistor-motor protection input, star-delta control and output relay for standstill indication. Brake current indicator. Removable terminals
The electronic motor brake device GB 9034 of the MINISTOP series by Dold is a device for wear-free braking of three-phase and alternating current asynchronous motors. It is used in drives that must be reliably braked for safety and functional reasons. The device enables precise control of the braking process through adjustable parameters and integrated monitoring functions. The variant GB9034/0111 is designed for a rated braking current of 200 A at a rated voltage of AC 400 V and complies with the standard IEC/EN 60947-4-2. The width is 110 mm, enabling compact mounting in enclosures.
Applications
The motor brake device is suitable for drives in various industrial sectors, including sawmills, centrifuges, woodworking machines, textile machines, and conveyor systems. It is used where short coast-down times and safe, reliable braking are required. The application is particularly relevant in systems where uncontrolled motor coast-down would be dangerous or functionally disruptive. The device variant supports braking current monitoring, thermistor motor protection inputs, star/delta control, and a standstill indicator relay. The braking current indicator enables visual monitoring of the operating status.
Functions and Equipment in Detail
The device operates with DC braking via a single-phase rectifier and generates a braking current adjustable up to 600 A. The braking time is also adjustable and can last up to 320 seconds. Braking is performed via an external brake contactor, which is controlled through terminals 1/2. The safety time interval between switching off the motor contactor and switching on the brake contactor prevents damage caused by induced voltages. A potential-free alarm output signals if the motor has not come to a standstill within the maximum braking time. Automatic standstill monitoring checks the motor status and switches off the braking current as soon as the motor stops.
Technology Explained Simply
The operating principle is based on converting the mains voltage (AC 400 V) into a DC voltage, which is applied to the stator winding of the motor via terminals U and V. This generates a braking torque that slows down the motor. Control is performed via terminals L1-L2 for the supply voltage and terminals 6-7 for the starter contact (normally open contact of the motor contactor). The ready LED indicates that the supply voltage is present. The plug-in control terminals facilitate installation and maintenance. Temperature monitoring protects the device and motor from overheating.
Compatibility and Accessories
The device is suitable for all asynchronous motors and can be integrated into existing systems. The variant GB9034/0111 is designed without auxiliary voltage. Functions such as star-delta control, thermistor motor protection, and standstill indicator relay are optionally available. The braking current indicator is integrated. The devices are designed for use in industrial environments and comply with the UKCA certification.
Mounting and Installation
Mounting is performed in an enclosure. The supply voltage is connected to terminals L1-L2. Motor connections are made to U, V, W. The external brake contactor is controlled via terminals 1-2. The interlock for the motor contactor is connected via terminals 8-9. Terminals 6-7 serve as the starter contact. The terminal connections are plug-in, simplifying installation and maintenance. The devices are designed for use in industrial systems and do not require additional auxiliary voltages.
Advantages in Operation
The device offers higher safety through shorter coast-down times and more economical operation through wear-free and maintenance-free operation. Easy installation, even in existing systems, reduces mounting time. Adjustable parameters allow individual adaptation to specific applications. The integrated standstill monitoring and alarm output increase system reliability. Temperature monitoring protects the device and motor from damage due to overheating. The width of 110 mm enables compact mounting in enclosures.