Further information for Dold 0060545 IL9171.12/801 3/N AC400/230V 0,85UN undervoltage relay
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
3/N AC 500 / 290 V
Output contacts
2 C/O contacts
Width
17,5 mm
Type
IL 9171
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3/N AC 400 / 230 V
Response value
0,85 Un
Time delay
without
Approvals and Markings
CCC
Variant
With N. NC circuit operation. Without time delay. Fixed response value. For switching small loads
The Dold undervoltage relay IL9171.12/801 is an industrial device for monitoring three-phase power networks for undervoltage. It is used for network monitoring and enables switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 and DIN VDE 0108. The relay operates on the rest current principle, in which the output relay is not activated in the event of a fault, and is designed for use in installation and industrial distribution systems. The width is 17.5 mm, and the device is designed for a rated voltage of 3/N AC 400/230 V. It features two changeover contacts as output contacts and can operate without auxiliary voltage.
Applications
The relay is designed for monitoring 3-phase networks, but can also be connected single-phase. It is used to automatically switch to a backup supply in the event of undervoltage or phase loss. The application is particularly in safety systems, where continuous power supply is required for emergency lighting or emergency power units. The IL9171.12/801 variant is specifically designed for switching small loads.
Functions and equipment in detail
The device detects undervoltages below a fixed pickup value of 0.85 times the rated voltage. The pickup delay is activated, meaning the relay does not react immediately to a voltage drop, but after a short delay. The contact position is indicated by an LED display, with a yellow LED lighting up when the output relay is activated (contacts 11-14 closed). Phase sequence is arbitrary, which makes installation flexible. The device is equipped with a neutral conductor connection, allowing voltage measurement between each phase and the neutral conductor.
Technology explained simply
Measurement is performed via the arithmetic mean of the voltage of each phase relative to the neutral conductor. For variants without neutral conductor connection, voltage is measured between L1 and L3 relative to L2 (IK/SK 9171) or between L1 and L2 relative to L3 (IL/SL 9171). For single-phase connection, terminals L1, L2 and L3 must be connected. The maximum rated voltage is 3/N AC 500/290 V. The frequency range is between 45 and 65 Hz. The device is certified to IEC/EN 60255-1 and meets requirements for electrical equipment in measurement and monitoring technology.
Compatibility and accessories
The relay is designed for use in installation distributors according to DIN 43 880. It is available in I form, which has a depth of 59 mm and terminals located at the bottom. The width of 17.5 mm allows mounting in standard distributors. No accessories or additional connections are required, as the device is designed as a standalone monitoring module.
Mounting and installation
Mounting is done in standard installation distributors with DIN rail. The terminals are located at the bottom, which facilitates integration into existing control systems. Wiring is done via the designated terminals for phases L1, L2, L3 and the neutral conductor N. The contacts are designed for switching small loads, with a contact rating up to 4 A. The gold-plated contacts are optimized for low loads; however, the plating may burn off at higher currents.
Advantages in operation
The relay provides reliable network monitoring without additional auxiliary voltage. The LED display allows for quick visual control of the operating status. The fixed pickup voltage of 0.85 Un ensures a clear and reproducible response to voltage drops. The form factor with 17.5 mm width enables compact mounting in distributors. The rest current principle ensures that the output relay is not activated in the event of a fault, increasing safety.
Approvals and markings
The device carries the CCC approval and complies with standards IEC/EN 60255-1 as well as DIN VDE 0100-710 and DIN VDE 0108. The rated consumption values are approximately 8 VA for the IL variant. The overload capacity is 1.15 times the rated voltage continuously. The hysteresis is approximately 4 %, ensuring stable switching behavior during voltage fluctuations.