Further information for Dold 0060265 insulation monitor IL5880.12/300 220-240V
Technical data
Enclosure design
Distribution board
IMD type
AC
Nominal voltage IT system
AC 0 - 500 V
Response value
5 - 500 kΩ
Response value type
Adjustable
Width
35 mm
Type
IL 5880
Earth fault indicator
Variant
Alarm value
5 - 100 kOhm
Auxiliary voltage
AC 220 - 240 V 50 - 400 Hz
Contact equipping
2 x 1 changeover contact
Prewarning value
10 kOhm - 5 MOhm
Approvals and Markings
UKCA, CCC
Variant
For mobile generator sets
The insulation monitor IL5880.12/300 AC50-400HZ 220-240V from Dold is a device for monitoring insulation resistance in ungrounded AC and three-phase networks (IT systems) with a rated voltage of AC 0 to 500 V. It is designed for early detection of insulation faults to ensure preventive fire and system protection. This variant is specifically designed for mobile power generators and complies with the standard DIN VDE 0100-551. The device is powered by a separate auxiliary voltage of AC 220 to 240 V at 50 to 400 Hz, enabling monitoring of de-energized systems as well.
Applications
This insulation monitor is intended for pure AC and three-phase networks in the frequency range of 10 to 10000 Hz. It is particularly suitable for mobile power generation systems, industrial plants, and railway applications. Monitoring is also possible with de-energized loads, such as motor windings in emergency power devices that must be activated in case of emergency.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts for signaling faults. The trip threshold for earth fault (RAL) is adjustable via a potentiometer on the front panel and ranges from 5 to 100 kΩ. Additionally, an adjustable warning threshold (VW) is available in the range of 10 kΩ to 5 MΩ, enabling early warning of impending insulation faults. The function of the output relays is programmable, allowing selection between memory and hysteresis behavior. Operational readiness is indicated by a green LED, an insulation fault by a red LED, and the warning state by a yellow LED.
Technology Explained Simply
The insulation monitor operates on the principle of residual current, where the output relay is not activated in the event of a fault. This prevents unwanted shutdowns. The measuring circuit, auxiliary voltage, and output contacts are galvanically isolated, ensuring high safety and immunity to interference. Indication is provided via LEDs, visually signaling the operating status. An integrated reset and test button allows manual resetting and testing of the device. External reset and test buttons can be connected to simplify operation in complex installations.
Compatibility and Accessories
The device is designed in the IL 5880 form factor, intended for installation and industrial distributors according to DIN 43880. The width is 35 mm, the depth is 61 mm, and the connection terminals are arranged at the bottom. Mounting is done via DIN rail or screws. The variant IL5880.12/300 is specifically designed for mobile power generators and meets the requirements of DIN VDE 0100-551. The devices are certified according to IEC/EN 61557-8 and carry the approval marks UKCA and CCC.
Mounting and Installation
Installation is carried out in standard installation distributors or industrial distributors according to DIN 43880. The connection terminals are intended for connection to the monitored IT system, the protective earth conductor (PE), and for external test and reset buttons. The auxiliary voltage is supplied via terminals A1 and A2. Mounting is done either on the DIN rail or by screw fastening.
Operational Advantages
The insulation monitor provides reliable and early detection of insulation faults, preventing damage to systems and fire hazards. The simple adjustment of trip thresholds and clear visual indication simplify maintenance and operation. Galvanic isolation and the residual current principle enhance safety and prevent unwanted shutdowns. The programmability of relay functions allows flexible adaptation to different applications.
Approvals and Markings
The device complies with standards IEC/EN 61557-8 and DIN VDE 0100-551. The approval marks UKCA and CCC are affixed to the device, confirming compliance with applicable safety and quality requirements.
Enclosure Design and Mounting
The enclosure design is intended for installation distributors. The width is 35 mm, the depth is 61 mm. The connection terminals are arranged at the bottom, facilitating installation in standard distributors. Mounting is done via DIN rail or screws.
Function of Output Relays
The function of the output relays is programmable. In memory mode, the relay remains activated after triggering until manually reset. In hysteresis mode, the relay resets automatically once the insulation resistance rises above the trip threshold again. Selection is made via terminals LT1 and LT2, where a bridge between LT1 and LT2 activates hysteresis behavior.
Connection Terminals and Signal Description
The connection terminals are assigned as follows: A1 and A2 for auxiliary voltage, L for the monitored IT system, PE for the protective earth conductor, PT for the external test button, LT1 and LT2 for external reset buttons or programming. The output contacts 11, 12, 14 and 21, 22, 24 serve as changeover contacts for signaling warning (VW) or alarm (AL). The LED indicators signal operational readiness (green), insulation fault (red), and warning state (yellow).