Further information for Dold 0060035 RP5995S/100 AC230V expansion module
Technical data
Alarm inputs
8
Alarm inputs extendable up to
88
Enclosure design
Distribution board
Operating principle
De-energized on trip, Energized on trip
Optical signal
LED
Special features
Bus-compatible, Configurable
Width
70 mm
Type
RP 5995
Operate delay
Optional buzzer
Variant
Contact equipping
2 x 1 NO contact
Nominal voltage
AC 230 V
Terminal type
screw terminal fixed
Variant
RS485 Bus isolated
The Dold RP5995S/100 AC230V ERWEITERUNGSMOD. is an expansion module for the new-value/first-value/collective fault alarm system RP 5995, developed for use in industrial monitoring systems. It serves to extend the fault alarm inputs in existing installations and enables the integration of additional sensors or switching devices into a central alarm system. The module is designed for a nominal voltage of AC 230 V and has a width of 70 mm, making it suitable for installation in standard distribution boxes. The enclosure type as an installation distributor allows for easy mounting in existing enclosures.
Applications
The module is used in production plants, manufacturing environments, and industrial process installations where rapid fault localization and reduction of production downtimes are required. It is part of a bus-capable system that communicates via a galvanically isolated RS485 bus, ensuring reliable data transmission even in electrically disturbed environments. The expandability from 8 to up to 88 fault alarm inputs makes it flexible for different installation sizes and complexities.
Functions and Equipment in Detail
The expansion module features 8 fault alarm inputs, each equipped with an LED for optical indication. The inputs can be operated in either current-on or current-off principle, with the triggering principle being adjustable. The response delay of the alarm inputs is also configurable and can be set between 0 and 10 seconds to avoid false triggers. The front of the module provides reset buttons for horn, fault alarm, and collective alarm, which can be used depending on system settings. An external reset button connection is also available to enable operation from remote locations.
Technology Explained Simply
The galvanic isolation of the RS485 bus ensures that electrical disturbances in the network are not transmitted to the module, increasing stability and reliability. The configurability of operating modes – such as new-value alarm, first-value alarm, or collective fault alarm (memory or non-memory) – allows adaptation to specific installation requirements. The contact configuration consists of 2 x 1 normally open contacts, used for controlling relays or external signal devices. The fixed screw terminal ensures a secure and durable connection for the wiring.
Compatibility and Accessories
The module is designed as an expansion for the base module RP 5994 and can be used in combination with alarm panels such as EH 5994 or EH 5995. These panels offer additional display and control options, with the EH 5994 integrating reset buttons for horn and collective alarm, while the EH 5995 does not include buttons. As an accessory, the alarm device RK 8832 is available, which generates acoustic signals. Using a text panel EH 5996 enables individual labeling of alarms.
Mounting and Installation
Mounting is carried out in a standard distribution box. The width of 70 mm corresponds to the standard module format for DIN rail mounting. The terminals are fixed screw terminals, ensuring a secure connection. Wiring is done according to the circuit diagrams in the datasheet, with connections for fault alarm inputs, relay outputs, and the RS485 bus clearly marked. Configuration is done via a rotary switch for addressing, which is set during commissioning.
Advantages in Operation
The expandability up to 88 inputs and the flexible configuration of operating modes provide high adaptability to different installations. Optical indication via LEDs and the option for remote reset increase efficiency in fault resolution. The galvanic isolation of the bus ensures robust communication, and the adjustable response delay reduces the number of false alarms. The module thus supports rapid fault localization and contributes to minimizing production outages.