Further information for Dold 0059711 GF9016 3AC50/60Hz 400V 22kW soft starter
Technical data
Extra functions
Mains monitoring, Temperature monitoring
For three-phase motors, 400 V up to
22 kW
Load voltage up to
3AC 400 V
Width
45 mm, 52,5 mm
Type
GF 9016
Signalling output
Variant
Auxiliary voltage
Without
Mains / motor voltage
3AC 400 V
Nominal motor power
22 kW
Approvals and Markings
UKCA
The soft starter GF 9016 from Dold is an electronic control device for smooth start-up and shut-down of three-phase asynchronous motors. It reduces mechanical stress in the drive system and enables jerk-free operation, particularly for motors with a rated power up to 22 kW at a supply voltage of 3AC 400 V. The device operates without auxiliary voltage and is designed in accordance with the standard IEC/EN 60947-4-2. It is intended for use in industrial plants where controlled start-up and braking phases are required to minimize wear and damage to drive components.
Applications
This device is suitable for drives with gear, belt, or chain transmission, for example in conveyor belts, fans, pumps, compressors, woodworking machines, centrifuges, packaging machines, and door drives. It is particularly used where direct start-up with high starting torque would cause mechanical stress. The soft shut-down function extends the natural braking time to avoid abrupt stopping and associated mechanical stress.
Functions and equipment in detail
The device controls two motor phases via phase-cut control using power semiconductors (thyristors). This allows the current and torque to be gradually built up during start-up, ensuring a jerk-free start. After start-up, the power semiconductors are bypassed via internal relay contacts to minimize power losses in the device. The W3 circuit configuration is also possible.
Technology explained simply
Control is performed via an electronic ramp control that gradually increases the voltage on two phases. The third phase is connected directly, resulting in a two-phase motor control. The integrated mains monitoring and temperature monitoring ensure safe operation. In case of faults, a yellow LED flashes with a specific pattern indicating error codes such as supply voltage fault, overload, electronic fault, or phase fault. A green LED indicates the ready-to-operate status. The alarm outputs (X5/X6 and X7/X8) allow connection to external controls to signal faults or the bypassed state.
Compatibility and accessories
The device is designed for three-phase asynchronous motors operated at 3AC 400 V. The maximum motor power is 22 kW. The width is 52.5 mm, which is specified for the power class up to 22 kW.
Mounting and installation
Mounting is done in standard control panels. The terminal markings include the supply voltage (L1, L2, L3), motor voltage (T1, T2, T3), and control and signal terminals (X1 to X8). Settings for start-up time, shut-down time, and start-up voltage are adjusted via the control elements on the device. Installation requires no auxiliary voltage, as the device is connected directly to the mains voltage.
Advantages in operation
By reducing starting currents, the supplying network is relieved. Mechanical components in the drive system experience less wear, extending the service life of motors and drives. Simple mounting and space-saving installation facilitate integration into existing plants. The integrated monitoring and fault indication via LED flash codes enable quick diagnosis in case of operational faults.