Further information for Dold 0059421 load monitor 3AC400V AC800mA
Technical data
1- / 3-phase
1, 3
Enclosure design
Switch cabinet
Measuring range max.
40 A (37 kW)
Output contacts
2 x 1 C/O contacts
Width
45 mm
Type
BH 9097
Operate delay
Variant
Auxiliary voltage
Without
Contact equipping
2 x 1 changeover contact
Nominal current max
AC 800 mA
Nominal voltage
3AC 400 V
Variant
3-phase without auxiliary supply. Start up delay time 0 - 30 s
The load monitor BH 9097.38/0013AC400VAC800MA from Dold is an industrial monitoring device of the VARIMETER series, designed for continuous monitoring of the load of electrical drives, particularly motors. The device monitors active power and responds to exceeding or falling below adjustable threshold values by activating output relays. It is designed for use in enclosures and is suitable for applications with variable motor loads, where early detection of load anomalies is important to avoid failures and ensure operational safety.
Applications
The load monitor is designed for monitoring motors up to 22 kW at 400 V and up to 37 kW at 690 V. It is used in industrial plants where reliable load monitoring is necessary to detect overloads, underloads, or malfunctions of electrical consumers. Due to the single-phase measurement principle, symmetrical loading of all three phases is assumed, which is typical for motor loads. The device is therefore particularly suitable for drives with even load distribution.
Functions and Equipment in Detail
The device features two output relays, each with a single changeover contact, used to signal two different load conditions. The threshold values P1 and P2 can be set via rotary switches as absolute values in watts. Configuration is done via DIP switches, allowing selection between underload and overload monitoring (P1min/P2max) and overload monitoring with a warning stage (P1max/P2max). The relays can be switched between operating current principle (activated in fault condition) and rest current principle (not activated in fault condition). Two LEDs indicate the switching state of the relays: a green LED indicates mains voltage, while two yellow LEDs indicate the state of relays P1 and P2. The LEDs flash during response delay or during setting assistance, and remain lit continuously when the respective relay is active.
Technology Explained Simply
Measurement is performed according to the principle of active power measurement. The device detects the load via mains voltage and current consumption and compares it with the set threshold values. An adjustable response delay tv suppresses short-term load fluctuations and prevents false tripping. A common adjustable start-up bypass time ta (0 to 30 seconds) prevents the device from reacting immediately during motor start-up, which typically causes short-term load peaks. Automatic range switching enables a wide measurement range up to 40 A without requiring an external current transformer. Configuration is done via DIP switches, which also control the memory behavior (automatic or manual).
Compatibility and Accessories
The device is designed for use in single-phase and three-phase systems, with the three-phase variant requiring symmetrical loading. It is rated for a nominal voltage of 3AC 400 V and can monitor loads up to 40 A. The maximum nominal power is 37 kW at 690 V. The width is 45 mm, making it suitable for standard enclosure mounting. It operates without auxiliary voltage, simplifying installation and reducing wiring effort.
Mounting and Installation
Mounting is done in an enclosure. Connections are clearly labeled, and settings are adjusted via rotary switches and DIP switches. A test/reset button facilitates commissioning and serves as a setting aid. The connection terminals are designed for connecting to mains voltage lines and loads. The LED indicators support diagnosis and verification of settings.
Advantages in Operation
The load monitor enables early detection of load anomalies, allowing preventive maintenance and avoiding costly damage. Reduced wiring and easy commissioning via the test/reset button reduce installation effort. Adjustable delay times and flexible relay function configuration increase adaptability to different applications. Operational safety and high system availability are ensured by continuous monitoring and clear fault signaling. Compliance with the standard IEC/EN 60255-1 ensures reliability and compatibility with other industrial devices.