| Technical data |
| 1- / 2-channel | 2 |
| Approvals | UL |
| Cat. / PL acc. to EN ISO 13849-1 | 3/e |
| Classification | For initiators |
| Forcibly guided output contacts max. | 1 NC contact, 2 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 4 A |
| Width | 45 mm |
| Type | BH 5932 |
| Variant |
| Contact equipping | 2 NO contacts, 1 NC contact |
| Nominal voltage | AC/DC 24 V |
| Response value | 60 IPM |
| Approvals and Markings | UL-listed C/US, TÜV, CCC |
| Variant | Without sensor detection. PNP-input. Fixed setting value |
The Dold speed monitor BH5932.22/010/61 AC/DC24V 60IPM is a safety-relevant monitoring switch for speed and standstill monitoring in industrial machines and plants. It is designed to detect machine movements that may pose a hazard to personnel or machine components, and ensures safe shutdown in case of deviation from the specified operating condition. The device is specifically designed for use with initiators such as inductive proximity switches and offers a fixed setpoint of 60 pulses per minute (IPM). The nominal voltage is AC/DC 24 V, making it suitable for use in standard industrial power supply systems.
Applications
The BH5932 is used in plants where monitoring of rotational and linear movements is required, for example in manufacturing, packaging technology, or automation technology. It ensures that moving machine parts are only operated when the speed has reached the specified value, and triggers a shutdown in case of standstill or unauthorized movement. The device is applied in safety-critical environments where reliability according to international standards is required.
Functions and equipment in detail
The device features a 2-channel design, enabling two independent monitoring channels. The contact configuration includes two normally closed contacts and one normally open contact, all of which are designed as forced-guided contacts. This design ensures that in the event of a fault in the internal circuit, the contacts remain in a defined, safe position, which is crucial for the safety function. The inputs are designed for PNP proximity switches, and this variant does not include initiator connection detection. A feedback circuit (X1–X2) enables monitoring of external contacts to implement additional safety functions.
Technology explained simply
The speed monitor operates with a fixed setpoint of 60 IPM, meaning it continuously monitors the speed of a drive and triggers a shutdown if this value is undershot. The output contacts are forced-guided, meaning they are mechanically linked to prevent malfunction due to internal circuit faults. The maximum thermal current rating is 4 A, defining the contact load capacity for connected loads. The width of 45 mm allows installation in standard control panels according to DIN.
Compatibility and accessories
The device is designed for use with inductive proximity switches of types NA 5001, NA 5002, NA 5005, and NA 5010. Connection options are detailed in the manufacturer’s data sheets, with combinations with initiators such as NA 5002.01.34 and NA 5005.01.34 only possible for devices without initiator connection detection. The terminal connections are designed for wires up to 2.5 mm² with ferrules DIN 46 228-1/-2/-3/-4. Connections are made via terminals In A / In B, with color coding (brown, blue, black) and assignment to contacts specified in the data sheet.
Mounting and installation
Mounting is done in standard control panels with a width of 45 mm. The terminal connections are designed for wires up to 2.5 mm², with the use of ferrules DIN 46 228-1/-2/-3/-4 recommended. Wiring is carried out according to the connection tables in the data sheet, with the assignment of colors (brown, blue, black, white) to inputs and outputs precisely defined. The devices are designed for use in industrial environments, with certifications UL-listed C/US, TÜV, and CCC confirming compliance with international safety standards.
Advantages in operation
The BH5932 offers high safety integrity with Category 3 and Performance Level e according to EN ISO 13849-1, as well as SIL 3 according to IEC/EN 62061. These certifications guarantee high reliability in safety-critical applications. The forced-guided contacts and 2-channel design increase fault tolerance and prevent unintended operating states. The clear structure of the terminal connections and support for PNP inputs facilitate integration into existing control systems. The operating voltage of AC/DC 24 V is widely used in industry, increasing compatibility with existing systems.
Approvals and safety standards
The device complies with the requirements of standards EN ISO 13849-1 (Category 3, PL e) and IEC/EN 62061 (SIL 3). Certifications UL-listed C/US, TÜV, and CCC confirm compliance with international safety standards. These certifications are essential for use in safety-critical plants, as they guarantee the reliability and fault-free operation of the device under real operating conditions. The classification as a device for initiators highlights its specific application in the field of safety-relevant monitoring systems.