Technical data
1- / 3-phase1
Enclosure designSwitch cabinet
Output contacts2 C/O contacts
Width35 mm
TypeSL 9277CT
Operate delayYes
Variant
Auxiliary voltageAC 220 - 240 V
Contact equipping2 changeover contacts
Measuring range0,5 - 100 A
Switching delay0,1 - 20 s
VariantSingle phase current relay with built in CT. De-energized on trip
The Dold SL9277.12CT is a single-phase current relay with an integrated passage current transformer, specifically designed for monitoring currents in alternating and three-phase power networks. It is used for detecting overcurrent and undercurrent and responds with an adjustable switching delay when the set switching point is exceeded or undershot. The device operates on the zero-current principle, whereby the output relay is not activated in the event of a fault, ensuring safe disconnection during malfunctions. The auxiliary voltage is AC 220–240 V, and the measurement ranges are between 0.5 and 100 A. The width is 35 mm, and the device is designed for mounting in enclosures, with both DIN rail and screw mounting options available.

Applications
This relay is suitable for use in industrial plants and railway applications where reliable current monitoring is required. It can be used in systems where continuous monitoring of current flow is necessary to detect overloads, underloads, or power failures at an early stage. The galvanic isolation between the auxiliary circuit and the measurement circuit enhances safety and prevents interference in the control circuit.

Functions and Features in Detail
The device features 2 changeover contacts as output contacts, which can be used for controlling auxiliary circuits or warning systems. The switching delay is adjustable in the range of 0.1 to 20 seconds, allowing short-term current peaks to be ignored or accounted for. The hysteresis is fixed at approximately 4 %, ensuring stable switching behavior and preventing the relay from switching uncontrollably due to minor fluctuations around the switching point.

Technology Explained Simply
The integrated passage current transformer enables current measurement without direct electrical connection to the main circuit. The current flows through the transformer, which converts it into a measurable signal. The relay compares this value with the set threshold and switches when the threshold is exceeded or undershot, after the set delay time. The LED indicators signal the operating status: a green LED indicates normal operation, a red LED for I max indicates overcurrent, and a red LED for I min indicates undercurrent. This visual feedback simplifies diagnosis and maintenance.

Compatibility and Accessories
The device is part of the VARIMETER series from Dold and can be used in systems that also utilize VARIMETER technology. It is designed for use in enclosures with mounting plate and cable duct. The S-type design (SL 9277CT) has a depth of 100 mm and top-mounted connection terminals, which facilitates integration into existing enclosures. The devices are certified to IEC/EN 60255-1, confirming compliance with international standards for electrical measuring instruments.

Mounting and Installation
Mounting is done either on DIN rail or by screw fastening. The connection terminals are arranged at the top, enabling easy wiring. Terminal markings are clearly defined: A1/A2 for auxiliary voltage, i/k for the current measurement circuit. The measurement range selection is done via jumpers on terminals Z1 to Z4. Installation requires no additional tools or components, as the device is fully pre-configured.

Advantages in Operation
The combination of adjustable thresholds, switching delay, and visual indicators offers high flexibility and reliability. The zero-current principle ensures that the output relay is not unintentionally activated in the event of a fault, which is particularly advantageous in safety-critical applications. The galvanic isolation between the measurement and auxiliary circuits enhances safety and prevents interference. The LED indicators allow for quick visual inspection of the operating status, simplifying maintenance and fault diagnosis.