| Technical data |
| Load current up to | 125 A |
| Load voltage up to | AC 600 V |
| Number of poles | 1-pole |
| On/Off Input Control | AC/DC, DC |
| Width | 45 mm |
| Type | PH 9260 |
| Variant |
| Control voltage | AC/DC 100 - 240 V |
| Load current | AC 50 A |
| Load voltage | AC 48 - 480 V |
| Semiconductor output | 1-pole |
| Variant | Switching at zero crossing. With heat sink |
The Dold semiconductor contactor PH9260.91/000/02 is an
AC semiconductor relay with a load voltage of AC 48 to 480 V and a load current of AC 50 A. It is designed for use in industrial applications where wear-free and noiseless switching of electrical loads is required. The device is operated via a control voltage of AC/DC 100 to 240 V and is standardly configured as
zero-voltage switching, meaning switching operations occur at the zero crossing of the sinusoidal mains voltage. This minimizes electrical interference and extends the service life of connected devices.
Applications
This semiconductor contactor is suitable for use in machine building, plastics and rubber industry, packaging technology, soldering systems, and the food industry. It is frequently used to control heating elements, motors, valves, and lighting systems. The zero-voltage switching configuration is particularly suitable for applications requiring gentle switching and disturbance-free operation. An optional peak-voltage switching variant is available, which is especially suited for switching transformers, as it avoids the high inrush current.
Functions and equipment in detail
The device features two antiparallel-connected thyristors responsible for the switching function. The
DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, reducing thermal stress on the component. An integrated
heat sink enables efficient dissipation of generated heat and is designed for mounting on a DIN rail. The
LED status indicator signals the state of the control input, simplifying operational monitoring. The connection terminals are designed as
box terminals, enabling secure and easy wiring.
Technology explained simply
In the zero-voltage switching variant, switching occurs at the zero crossing of the mains voltage, meaning the load circuit is only closed when the voltage reaches zero. This prevents arcing and reduces electromagnetic interference. The maximum peak blocking voltage is 1200 V or 1600 V, and the insulation voltage is 4000 V, ensuring high electrical safety. The device is compliant with
IEC/EN 60947-4-3 and designed for continuous operation. The operating temperature range is -20 °C to 40 °C, and the storage temperature range is -20 °C to 80 °C.
Compatibility and accessories
The semiconductor contactor is designed for use in industrial control and drive systems. It can be optionally equipped with
over-temperature protection, where a temperature limit switch (normally open) can be inserted into a designated slot on the underside. If a predefined temperature (e.g. 100 °C) is exceeded, the switch opens and protects the device from thermal overload. An example of a suitable temperature limit switch is the type UP62 – 100 from UCHIYA. Mounting is on a DIN rail, with the heat sink snapping directly onto the rail.
Mounting and installation
Mounting is on a standard DIN rail (DIN rail) using the integrated heat sink. The box terminals allow for easy and secure connection of wires. The width is 45 mm, enabling compact installation in enclosures. The touch protection class of the terminals is
IP20, providing protection against finger contact. The housing itself has a protection rating of
IP40, protecting against dust and splashing water.
Advantages in operation
The semiconductor contactor offers wear-free operation, as there are no mechanical contacts. This results in a long service life and reduced maintenance costs. The noiseless switching and minimized electromagnetic interference are advantages in sensitive production environments. The integrated LED indicator simplifies diagnosis and monitoring of the operational status. The DCB technology and heat sink ensure efficient heat dissipation, increasing the reliability of the device. Compliance with IEC/EN 60947-4-3 ensures adherence to industrial safety standards.