Further information for Dold 0059072 current relay BA9053/011 AC230V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9053
Operate delay
Variant
Auxiliary voltage
AC 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 0,1 - 1 A
Start up delay
Without
Switching delay
0 - 100 s
Approvals and Markings
UKCA, CCC
Variant
Overcurrent relay. De-energized on trip. Time delay at response value
The current relay BA9053/011 from Dold is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase AC networks. It operates on the zero-current principle, where the contact is closed in the normal state and opens when the set current value is exceeded. Device settings are adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The relay is designed for use in industrial and railway applications and serves for early detection of current anomalies to prevent electrical system failures and enhance operational safety.
Applications
The relay is used to monitor current consumption of electrical loads, for example in systems with motors, transformers, or other loads requiring a defined operating current. Measurement is performed in the range of AC 0.1 to 1 A, with the measurement range defined via terminals i1/k. The devices are calibrated for sinusoidal AC currents in RMS value and measure the arithmetic mean of the rectified measurement current. The application is in enclosures, with a width of 45 mm enabling compact mounting.
Functions and Equipment in Detail
The relay features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or warning signals. The switching delay is 0 to 100 seconds and is activated when the set value is exceeded. This delay prevents false alarms caused by short-term current peaks. The response delay is also integrated to ensure precise reaction to current changes. The auxiliary voltage is AC 230 V, allowing the device to be operated in standard mains voltage installations. The auxiliary circuits are galvanically separated from the measurement circuit, ensuring safe isolation and preventing interference.
Technology Explained Simply
Measurement is performed via an internal shunt resistor, which converts current into a proportional voltage drop. The devices are designed for a maximum continuous load of 0.7 A, with a maximum permissible current for 3 seconds at 1.8 A. The measurement frequency can reach up to 5 kHz, enabling accurate detection even for high-frequency signals. Settings are adjusted via rotary switches, allowing both the pickup value and the dropout value (hysteresis) to be set. The hysteresis depends on the set value and prevents contact flickering when current values are near the threshold.
Compatibility and Accessories
The relay is designed for use in single-phase systems and can be used as either an overcurrent or undercurrent relay, with the function determined by the threshold setting. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, i/k for the current measurement circuit, and contacts 11-14 and 21-24 for the two changeover contacts. The devices comply with IEC/EN 60255-1 and IEC/EN 60947-1 standards and carry the approvals UKCA and CCC. The LED indicator shows operational readiness (green LED) and activation of the output relay (yellow LED).
Mounting and Installation
Mounting is performed in enclosures, with a width of 45 mm enabling standard installation on DIN rails. The connection terminals are designed for direct cable connection. The auxiliary voltage is connected via terminals A1/A2, and the measurement current via i/k. Contacts 11-14 and 21-24 are used to connect to external control or signaling devices. Settings are adjusted on-site via the rotary switches on the front panel.
Advantages in Operation
Precise current monitoring combined with integrated switching delay ensures reliable fault detection. Galvanic separation between measurement and auxiliary circuits increases safety. The LED indicator allows for quick visual inspection of the operating status. Simple adjustment and robust construction ensure high operational safety and reduce maintenance requirements. The device is designed for high overload capacity, enabling reliable operation even under difficult operating conditions.